program can be set up.
31
Battery equalization voltage
29.2V (default)
Setting range is from 25.0V to
31.0V. Increment of each click
is 0.1V.
33
Battery equalized time
60min (default)
Setting range is from 5min to
900min. Increment of each
click is 5min.
34
Battery equalized timeout
120min (default)
Setting range is from 5min to
900 min. Increment of each
click is 5 min.
35
Equalization interval
30days (default)
Setting range is from 0 to 90
days. Increment of each click
is 1 day
36
Equalization
activated
immediately
Enable
Disable (default)
If equalization function is enabled in program 30, this program
can be set up. If “Enable” is selected in this program, it’s to
activate battery equalization immediately and LCD main page will
show “
”. If “Disable” is selected, it will cancel equalization
function until next activated equalization time arrives based on
program 35 setting. At this time, “
” will not be shown in LCD
main page.
37
Reset all stored data for PV
generated
power
and
output load energy
Not reset(Default)
Reset