PTR-24

CONTROL UNIT

English

INSTALLATION

2. 

Mounting/Substitution

2.1 

The unit is supplied ready-installed in the electrical box of 

the barrier.

To substitute the unit, proceed as follows:

IMPORTANT!

 Switch off the power supply. 

- Disconnect all the connections.

- Unscrew the retaining screws and remove the card.

- Fit the new card and tighten the retaining screws.

- Connect up.

- Switch on the power supply. Program the operating logic 

and save the remote controls.

Electric system set-up

2.2 

Before you install components you should prepare the electrical 

connections of the control and safety devices of the system. 

Follow the instructions given on the “

Electrical equipment setup 

diagram

 

in the instruction manual supplied with the barrier. 

Follow the instructions given in this manual and the instructions 

given on components already installed.

Warning

!

 The system must only be installed by 

skilled personnel qualifi ed in compliance with the regulations 
of the country of installation (CEI 64 - 8 / EN 60335-1 standards).

Electrical connections

2.3 

Warning

!

Switch OFF the mains power supply before you start 
connecting up.
Before you connect up the product and accessories, check 
them for damage.
IMPORTANT! Read and follow the instructions for all the 
components installed.

Check that all the connections are as speci

fi

 ed in the 

Layout diagram

. Check that the cables are connected to 

the correct inputs. Check that the minimum cable section 

is as speci

fi

 ed.

Warning

!

Faulty connections can cause equipment operating faults 
and may seriously damage the equipment. Failure to 
connect up the equipment correctly will void your guarantee.
Do NOT use intercom or telephone cable.
IMPORTANT: Complete all connections and checks before 
you connect up to the mains power supply.
The equipment must be earthed. Connect the earth to the 
earth terminals.

Connecting up to the mains power supply

2.4 

POWER SUPPLY

 - 230/[115 on demand] V AC monophase 

50/[60] Hz.

 Use a power supply cable with 3 wires and a minimum 

section of 1.5 mm

2

; the cable must comply with current 

electrical regulations. Choose the section of the cable to 

match the length of the line.

IMPORTANT ! Always install, upstream of the line, a mains 
switch which guarantees a multipole cut-off with minimum 
contact opening of 3 mm (connect it to a 6 A differential 
overload switch with sensitivity of 30 mA).

J1

RS232 serial connector/ Urmet interface connector for 

optional master-slave card

J3

Removable terminal board - power for 24 V DC motor 

output - 2-wire cables with minimum section of 1,5 mm2 

and tooled beam lighting programmable Output

J4

13 pin removable terminal board - connections for 

control and accessory inputs

1

 photocell test (if enabled) - 12 V AC output, max. 

connectable load 15W

3-4

 warning light - 24 V DC output with maximum load 

of 3 W for barrier warning light

5-4

 

fl

 ashing LED, 24 V DC - two-wire cable with min. 

section 1 mm

2

. DO NOT use other types of 

fl

 ashing light!

6-10

 pedestrian start (N.O.) (for twin barrier installations)

7-10

 24 V power supply for ACCESSORIES

8-10

 auxiliary safety (N.C.) (photocell, safety edge)

9-10

 Closing photocell input (N.C. safety contact)

11-12

 STOP (N.C. safety contact) command

13-12

 START (N.O.) opening and closing command

J6

Removable connector for transformer primaries 230/

[115] VAC

J7

Removable connector for connection to optional 

additional battery charger, for two 12 V, 9A/h or 1.3A/h 

batteries (no supplied)

J9

Removable terminal board - prepared for connections 

to motor encoder

J12

Connector for built-in receiver memory module

J18

Removable terminal board - input connections:

1-3 CLOSE (N.O.) closing command

2-3 auxiliary input for tooled beam lighting programmable 

Output managing 

J3

J20

Removable terminal board - limit switch connections

D55
D58

Limit switch warning LED (switches off when limit 

switch is triggered)

M1

Removable terminal board - mains power phase-

neutral-earth connection

DL1

FW and power supply ON warning LED

BATT

24 VDC battery connection

JRX

Connector for built-in receiver (

CAUTION

 This connector 

can only be plugged in one way. Ensure that the plug-in 

direction is correct. Do not force)

CN1

10-pin connector for PL-ECO receiver (alternative to 

built-in receiver)

CN2

3-pin Aprimatic connector for accessories; connection 

for radio card compatible with UNICO receiver 

(alternative to built-in receiver) - decoder access control

CN3

Terminal board for built-in receiver antenna

FS2

2 faston connectors for transformer secondaries (21 VAC) 

F1

Fuse for transformer primaries protection

F2

Fuse for external accessory protection (24VDC)

F3

Fuse for electronic circuit protection

DS1 DS2 DS3 DS4

:

 

LED display- for displaying parameters 

and parameter values

PROGRAMMING BUTTONS

:

YELLOW

 - ESC - to leave the current process (and to show the 

status of the barrier and the inputs on the display)

BLUE

 - SCROLL - use this to scroll through the options available

RED

 - OK - use this to open basic programming and to 

con

fi

 rm the option displayed

Card components

table 2 -  

Summary of Contents for PTR-24

Page 1: ...CK DES HANDBUCHS Dieses Handbuch wurde vom Hersteller verfasst und ist ein erg nzender Bestandteil des Produkts Es enth lt alle n tigen Informationen f r die Sensibilisierung der Monteure f r Fragen d...

Page 2: ...erme Schliessen Cierra BLACK Nero Black Noir Swarz Negro CLPh Fotocellula in chiusura Closing photocell Photocellule en fermeture Lichtschranke beim Schlie en Fotoc lula en cierre Flash Lampeggiatore...

Page 3: ...declina ogni responsabilit per le possibili inesattezze contenute nel presente manuale derivanti da errori di stampa o di trascrizione L azienda si riserva il diritto di apportare modifiche atte a mi...

Page 4: ...inosservanza della Buona Tecnica nella costruzione della struttura da motorizzare n delle deformazioni che dovessero intervenire nell utilizzo Un errata installazione pu essere fonte di pericolo Esegu...

Page 5: ...lo remoto DEC A decoder tag e tastiera Ricevente RPL ECO o Ricevitore Unico in alternativa alla ricevente integrata Possibilit di gestire 2 barriere contrapposte in modalit Master Slave l apparecchiat...

Page 6: ...30 mA J1 Connettore per la seriale RS232 interfaccia Urmet connettore scheda MASTER SLAVE OPZIONALE J3 Morsettiera estraibile potenza per uscita motore da 24 VDC cavi a 2 conduttori minimo 1 5 mm2 e...

Page 7: ...K TEST fotocellula non utilizzato Lampada spia CH1 GND CH2 GND Input aux CHIUDE Output aux Output aux Finecorsa Rosso Nero M MASTER M SLAVE GND ATTENZIONE i contatti N C devono essere ponticellati ver...

Page 8: ...a con STOP o in manovra successiva al riconoscimento ostacolo oppure funzionamento in EMERGENZA con batterie in mancanza di alimentazione di rete Lampada spia per la segnalazione remota dello stato de...

Page 9: ...l ciclo di funzionamento automatico 9 STOP ferma la barriera 9 START durante l apertura viene ignorato durante la chiusura fa riaprire durante il tempo di pausa fa ripartire da 0 il tempo di pausa poi...

Page 10: ...er utilizzare la Memory System ricevitore UNICO o la RPL ECO rimuovere la ricevente integrata a innesto e la relativa antenna vedi Schema dell apparecchiatura Inserire il ricevitore UNICOnel connettor...

Page 11: ...pengono P r e m o i l B L U p e r s c o r r e r e i v a l o r i disponibili p e r i l parametro Se decido di non modificare premo il giallo torno alla visualizzazione dei parametri fase o ROSSO ROSSO...

Page 12: ...Sicurezza in apertura 0 costa sensibile 1 fotocellula 0 1 1 AF Funzionamento in emergenza con batterie in mancanza di alimentazione segnalato da lampeggiatore a frequenza elevata 00 pu eseguire 3 mano...

Page 13: ...occa APERTA in pausa Come da para metro AA Blocca Chiude Inibisce chiusura Al disimpegno chiude come parametro Ab Blocca fino al disimpegno Blocca fino al disimpegno IN CHIUSURA Riapre Blocca Riapre R...

Page 14: ...ausiliario Costa sensibile Fotocellula CHIUSO Apre Apre il pedonale IN APERTURA Completa l apertura elimina eventuale comando chiusura memorizzato Blocca elimina eventuale comando chiusura memorizzat...

Page 15: ...APERTURA PEDONALE Apre tutto Blocca il pedonale Completa l apertura e chiude dopo tempo pausa Breve inversione e blocca Blocca Apre al disimpegno Breve inversione e blocca INCHIUSURA PEDONALE Apre tu...

Page 16: ...onale Chiude Breve inversione e blocca Blocca Apre al disimpegno Breve inversione e blocca IN CHIUSURA PEDONALE Apre tutto Riapre il pedonale Blocca il pedonale Riapre Riapre Blocca Chiude al disimpeg...

Page 17: ...eseguirelamanutenzionescollegarel automazione dalla rete di alimentazione mediante l interruttore differenziale dell impianto elettrico Se sono presenti le batteried emergenzadevonoessereanch essescol...

Page 18: ...r the user 32 EC conformity declaration 78 ABOUT THIS MANUAL Information This instruction manual describes the installation of the electrical components on the PTR 24 control unit only For instruction...

Page 19: ...ntry where the automation is installed The manufacturer of the device is not responsible for the non observance of professional standards of work in the construction of the power driven structure nor...

Page 20: ...ng of maintenance Suitable for fitting remote control devices including DEC A tag decoder and keypad PL ECO receiver Unico receiver as alternative to built in receiver Suitable for controlling two cou...

Page 21: ...tor for optional master slave card J3 Removable terminal board power for 24 V DC motor output 2 wire cables with minimum section of 1 5 mm2 and tooled beam lighting programmable Output J4 13 pin remov...

Page 22: ...V AC Power supply 230 V 50Hz 115 V 60 Hz 6 10 TRANSFORMER BLUE scroll RED OK PHASE EARTH NEUTRAL Red Black AUX Output AUX Output GND Limit switch Limit switch Photocell TEST Warning Light not used 24...

Page 23: ...with STOP either during operation after detection of obstacle or during EMERGENCY MODE operation with batteries following a power supply failure Warning light this is a remote signal indicating the c...

Page 24: ...during opening stroke is ignored during the closing stroke starts an opening stroke during the pause time restarts the pause time from 0 and at the end of the full pause time closes the rod 9 Closing...

Page 25: ...grammedremotecontrols usether trmenuontheadvancedprogrammingmenu seerelatedsection NOTE To confirm that you really want to cancel the programming press the RED button when the message SUREappears Afte...

Page 26: ...ng the displays are switched OFF Press the BLUE but ton to scroll t h r o u g h the values available for the pa rameter Ifyoudecidenottomakeanymodifications press the yellow button to display the para...

Page 27: ...n 1 REOPEN and stops in the open position 0 1 0 AE Safety device during opening 0 safety edge 1 photocell 0 1 1 AF Operation in emergency mode with batteries following a power supply failure indicated...

Page 28: ...on parameter Ab Blocks as long as the photocell is covered Blocks as long as the photocell is covered CLOSING Reopens Stops and blocks Reopens Reopens Stops and blocks When uncovered will close Reope...

Page 29: ...ecurity OBSTACLE DETECTED Auxiliary input Safety edge Photocell CLOSED Opens Opens pedestrian beam OPENING Complete the opening cleanes any saved closure input Stops and blocks cleanes any saved closu...

Page 30: ...nversion and block Stops and blocks When uncovered will open Short inversion and block PEDESTRIAN CLOSING Opens completely cleanes any saved closure input Opens pedestrian beam cleanes any saved closu...

Page 31: ...nversion and block PEDESTRIAN CLOSING Opens completely Pedestrian reopening Blocks pedestrian beam Reopens Reopens Stops and blocks When uncovered will close Reopens LOGIC MANNED parameter LO 5 keepin...

Page 32: ...or interrupt the photocell beam Every 6 months Aprimatic S p A via Leonardo da Vinci 414 40059 Villa Fontana di Medicina Bologna Italia Tel 39 051 6960711 fax 39 051 6960722 info aprimatic com www apr...

Page 33: ...garde pour l utilisateur 47 D claration de conformit 78 INTRODUCTION AU MANUEL D INSTRUCTIONS Informations Les pr sentes instructions concernent exclusivement l installation lectrique du syst me de c...

Page 34: ...de la structure motoriser et quant aux probl mes de d formation pouvant r sulter de son utilisation Une installation incorrecte peut constituer un danger Effectuer les interventions selon les instruc...

Page 35: ...ispositifs de contr le distance DEC A d codeur tag et clavier r cepteur PL ECO ou r cepteur Unico au lieu du r cepteur int gr Possibilit de g rer 2 barri res oppos es en mode Ma tre Esclave la platine...

Page 36: ...ornier extractible puissance pour sortie moteur de 24 V DC c bles 2 conducteurs minimum 1 5 mm2 et Sortie programmable clairage de la lisse outill e J4 Bornier extractible 13 p les connexions entr es...

Page 37: ...de course TEST Photocellule Voyant not utilis e 24 V DC Accessoires Commande clignotant Marche Pi ton 24 V DC Accessoires S curit en Ouverture Photocellule Terre Terre ARR T MARCHE au lieu de l ARR T...

Page 38: ...isme bloqu avecARR T ou en phase de man uvre suite la d tection d un obstacle ou fonctionnement en MODE D URGENCE sur batteries en cas de coupure de courant Voyant pour la signalisation distance de l...

Page 39: ...nt l ouverture est ignor e pendant la fermeture commande la r ouverture pendant le temps de pause fait repartir de 0 le temps de pause une fois le temps de pause coul la lisse se referme 9 cellule pho...

Page 40: ...esm morisations qui ont t confirm es sont enregistr es Il est possible d EFFACER toutes les t l commandes m moris es via le param tre r trdu menu de programmation avanc e voir paragraphe correspondant...

Page 41: ...l e s p o u r l e param tre Si aucune modification ne doit tre faite appuyer sur le bouton jaune retour la visualisation des param tres phase o ROUGE ROUGE ROUGE ROUGE BLEU BLEU o n p q r s Appuyersu...

Page 42: ...n ouverture 0 bord sensible 1 cellule photo lectrique 0 1 1 AF Fonctionnement en mode d urgence sur batteries en cas de coupure de courant signal par le clignotant fr quence rapide 00 peut effectuer 3...

Page 43: ...est d gag se ferme comme d fini par le param tre Ab S arr te jusqu ce que tout soit d gag S arr te jusqu ce que tout soit d gag EN FERMETURE Se rouvre S arr te Se rouvre Se rouvre S arr te Se ferme qu...

Page 44: ...e pi ton EN OUVERTURE Ach ve l ouver ture limine la commande de fermeture ventuel lement m moris e S arr te limine la commande de fermeture ventuel lement m moris e Ach ve l ouverture et se ferme apr...

Page 45: ...pi ton Ach ve l ouverture et se ferme apr s le temps de pause Br ve inversion et s arr te S arr te S ouvre quand tout est d gag Br ve inversion et s arr te EN FERMETURE PIETON S ouvre compl te ment l...

Page 46: ...te S arr te S ouvre quand tout est d gag Br ve inversion et s arr te EN FERMETURE PIETON S ouvre compl te ment Rouvre l ouverture pi ton Bloque l ouverture pi ton Se rouvre Se rouvre S arr te Se ferme...

Page 47: ...BLE DE L ENTRETIEN 6 Il est rappel que selon le D cret Minist riel 98 37 CEE il est n cessaire apr s l installation de remplir une D claration de conformit de la machine et une Proposition d entretien...

Page 48: ...ng 62 7 Hinweise f r den Benutzer 62 Konformit tserkl rung 78 VORWORT ZU DIESER ANLEITUNG Informationen DievorliegendeAnleitungbetrifftausschlie lichdieelektrischeInstallationdesSteuersystemsmit Steue...

Page 49: ...die bei der Benutzung auftreten Eine fehlerhafte Installation kann eine Gefahrenquelle darstellen Die Arbeiten m ssen nach den Angaben des Herstellers durchgef hrt werden Bevor mit der Installation be...

Page 50: ...ur Empf nger PL ECO oder Empf nger Unico alternativ zum integrierten Empf nger M glichkeit zur Steuerung von 2 gegen berliegenden Schranken mit Schleusenfunktion Master Slave die MASTER Einrichtung st...

Page 51: ...erAusgang f r Schranke umger stet Beleuchtung J4 Abziehbare 13 polige Klemmleiste Anschl sse der Eing nge f r Steuerung und Zubeh r 1Lichtschrankentest nachAktivierungdesentsprechenden Parameters 12VW...

Page 52: ...GS Zubeh r Blinkleuchtensteuerung START Fu g nger 24 V GS Zubeh r Sicherheitseinrichtung beim ffnen Lichtschranke GND GND STOPP START alternativ zum STOPP AUX Ausgang Plan der Steuereinheit und Ansch...

Page 53: ...rderlich leuchtet mit Dauerlicht Schranke gestoppt mit STOPP oder bet tigt nachAusl sung der Hinderniserkennung oder NOTBETRIEB mit Batterien bei Stromausfall Kontrollleuchte f r die Fernanzeige des S...

Page 54: ...nke 9 START beim ffnen wird ignoriert beim Schlie en ffnet erneut w hrend Pausenzeit Pausenzeit startet bei 0 nachAblauf der Pausenzeit schlie t die Schranke erneut 9 Sicherheitslichtschranke beim Sch...

Page 55: ...e best tigt worden sind werden gespeichert DasL SCHENallergespeichertenHandsenderist berdenParameter r trimMen dererweitertenProgrammierungm glich sieheentsprechendenAbschnitt Hinweis ZumBest tigender...

Page 56: ...e durchzusehen Wenn Sie keine nderungen vornehmen m chten dr cken Sie die gelbe Taste auf diese Weise kehren Sie zur Anzeige der Parameter zur ck Schritt o ROT ROT ROT ROT BLAU BLAU o n p q r s Dr cke...

Page 57: ...tan 0 1 0 AE Sicherheitseinrichtungbeim ffnen 0 Sicherheitskontaktleiste 1 Lichtschranke 0 1 1 AF Notbetrieb mit Batterien bei Stromausfall Blinkleuchte blinkt schnell 00 kann 3 Vorg nge ausf hren dan...

Page 58: ...Wenn nicht mehr belegt schlie en wie Parameter Ab Stoppen bis nicht mehr belegt Stoppen bis nicht mehr belegt BEIM SCHLIESSEN Erneut ffnen Stoppen Erneut ffnen Erneut ffnen Stoppen Schlie en wenn nic...

Page 59: ...nt Hilfsein gang Sicherheits kontaktleisteLichtschranke GESCH LOSSEN ffnen ffnen Fu g nger BEIM FFNEN Vollst ndig ffnen L schen eines evt gespeicherten Schlie befehls Stoppen L schen eines evt gespeic...

Page 60: ...chlie en nach Pausenzeit Kurze Umkehr und stoppen Stoppen ffnen wenn nicht mehr belegt Kurze Umkehr und stoppen beim SCHLIE EN FU G NGER Vollst ndig ffnen L schen eines evt gespeicherten Schlie befehl...

Page 61: ...urze Umkehr und stoppen Stoppen ffnen wenn nicht mehr belegt Kurze Umkehr und stoppen beim SCHLIE EN FU G NGER Vollst ndig ffnen Fu g nger erneut ffnen Stoppen Fu g nger Erneut ffnen Erneut ffnen Stop...

Page 62: ...rnisse entfernen durch die der Lichtstrahl der Lichtschranken st ndig unterbrochen wird z B ste oder Geb sche 6 Monate Achtung Vor Wartungsarbeiten die Stromversorgung ber den FI Schalter der Elektroa...

Page 63: ...do 77 7 Advertencias para el usuario 77 Declaraci n de conformidad 78 INTRODUCCI N AL MANUAL DE INSTRUCCIONES Informaciones Estas instrucciones se refieren nicamente a la instalaci n el ctrica del sis...

Page 64: ...la estructura que se debe motorizar ni de las deformaciones que pudieran ocurrir durante la utilizaci n Una instalaci n equivocada puede ser una fuente de peligro Al ejecutar las operaciones observar...

Page 65: ...or tag y teclado receptor PL ECO o receptor Unico como alternativa al receptor integrado Posibilidad de controlar 2 barreras opuestas en el modo Master Slave el equipo MASTER gestiona el equipo SLAVE...

Page 66: ...tor tarjeta MASTER SLAVE OPCIONAL J3 Regleta de bornes extra ble potencia para salida motor de 24 V DC cables de 2 conductores de m nimo 1 5 mm2 y Salida programable iluminaci n barra equipada J4 Regl...

Page 67: ...o intermitente START peatonal 24 V DC Accesorios Seguridad en apertura Fotoc lula GND GND STOP START comoalternativaaSTOP Salida AUX Final de carrera ESCLAVE ATENCI N los contactos N C deben puentears...

Page 68: ...ci n bloqueada con STOP o en fase de maniobra siguiente al reconocimiento del obst culo o bien funcionamiento en EMERGENCIA con bater as y en ausencia de la alimentaci n de red Piloto para la se aliza...

Page 69: ...onamiento autom tico 9 STOP para la barrera 9 START durante la apertura se ignora durante el cierre hace reabrir durante el tiempo de pausa hace reiniciar de 0 el tiempo de pausa cuando vence el tiemp...

Page 70: ...han confirmado se guardar n El BORRADO de todos los mandos a distancia es posible mediante el par metro r tren el men de programaci n avanzada ver el p rrafo correspondiente nota para confirmar el bor...

Page 71: ...disponibles p a r a e l par metro Si decido no modificar pulso la tecla amarilla regreso a la visualizaci n de los par metros fase o ROJA ROJA ROJA ROJA AZUL AZUL o n p q r s Pulso la tecla ROJA duran...

Page 72: ...rtura 0 perfil de seguridad 1 fotoc lula 0 1 1 AF Funcionamiento en emergencia con bater as en ausencia de alimentaci n indicado por el parpadeo acelerado 00 puede ejecutar 3 maniobras luego se para c...

Page 73: ...e desactiva cierra como indica el par metro Ab Bloquea hasta que se desactive Bloquea hasta que se desactive EN CIERRE Vuelve a abrir Bloquea Vuelve a abrir Vuelve a abrir Bloquea Cierra cuando se des...

Page 74: ...c lula CERRADO Abre Abre el tr nsito peatonal EN APERTURA Completa la apertura y elimina el posible mando de cierre memorizado Bloquea elimina el posible mando de cierre memorizado Completa la apertur...

Page 75: ...a la apertura y cierra transcur rido el tiempo de pausa Breve inversi n y bloquea Bloquea Abre cuando se desactiva Breve inversi n y bloquea ENCIERRE PEATONAL Abre todo elimina el posible mando de cie...

Page 76: ...bloquea Bloquea Abre cuando se desactiva Breve inversi n y bloquea EN CIERRE PEATONAL Abre todo Vuelve a abrir el tr nsito peatonal Bloquea el tr nsito peatonal Vuelve a abrir Vuelve a abrir Bloquea C...

Page 77: ...nto desconectar la automatizaci n de la red de alimentaci n mediante el interruptor diferencial de la instalaci n el ctrica En caso de que estuvieran presentes tambi n hay que desconectar las bater as...

Page 78: ...78...

Page 79: ...79...

Page 80: ...80 Aprimatic S p A via Leonardo da Vinci 414 40059 Villa Fontana di Medicina Bologna Italia Tel 39 051 6960711 fax 39 051 6960722 info aprimatic com www aprimatic com...

Reviews: