AQUAKOND AKY
CONDENSING BOILER
11
code HC0048.10GB ed.B-1811
AKY
* Abbreviation compliant with reg. EU/811/2013.
1 The boiler is supplied as standard with B23P terminal; other configurations are possible using accessories.
2 Reg. EU/813/2013 art.2 point 20. It is calculated starting from the weighted average of useful efficiency to the rated heat output and of the useful
efficiency at 30% of rated heat output, expressed in %. For calculation purposes, the efficiency value is referred to the higher calorific value [Hs].
3 Value referred to cat. H (gas G20) with Burner for Switzerland setting. For further details refer to page 34 table 6.2 (gas settings).
4 CO and NOX values refer to the average weighted value of emission between maximum and minimum rated heat output according to the product
standard. Values referred to cat. H (gas G20).
5 The boiler is supplied as standard with C63 configuration; other configurations are possible using accessories available from our catalogue.
6 AKY100 for Switzerland is weakened: Burner heat output [Hi] [72/45°C] MAX: 92 kW and MIN: 20.5 kW.
BOILER
AKY034
AKY050
AKY070
AKY100
HC00046 ET
012
Type of equipment
B23P¹-B53P-C43-C53-C63-C83
B23P -C63
5
EC approval
P.I.N.
0476CR1226
Seasonal space heating energy efficiency -
[Reg.813/2013/EC]²
h
s
92.6
90.8
91.3
92.5
Energy efficiency class [Reg.811/2013/EC]
A
-
NOx class [EN 15502-1]
6
Boiler yields
Symbol*
MAX
MIN
MAX
MIN
MAX
MIN
MAX
MIN
Burner heat output [Hi]
Qn
kW
34.8
8.0
49.0
8.1
65.0
11.0
96.0
6
21.0
6
Useful heat output [Hi] [80/60°C]
P4
kW
34.2
7.9
47.4
7.8
63.4
10.7
92.8
21.2
Useful heat output [Hi] [50/30°C]
kW
36.8
8.6
51.4
8.5
67.9
11.8
100.1
23.1
Useful heat output at 30% of load [Hi] [50/30°C]
P1
kW
11.4
15.7
21.0
31.1
Useful heat output [Hi] [72/45°C]
Pn
kW
35.2
8.3
48.9
8.3
65.3
11.4
96.2
22.2
Useful efficiency [Hi] [80/60°C]
η4
%
98.3
98.2
96.8
95.7
97.5
97.4
96.7
98.6
Useful efficiency [Hi] [50/30°C]
%
105.8
106.9
104.8
105.5
104.5
107.4
104.3
107.6
Useful efficiency at 30% of Pn [Hi] [50/30°C]
η1
%
108.9
106.7
107.5
108.1
Useful efficiency [Hi] [72/45°C]
%
101.1
103.3
99.7
101.9
100.5
103.8
100.2
103.3
Flue losses with burner on [80/60°C]
%
2.6
1.4
2.7
1.0
2.7
0.9
3.3
1.4
Heat loss in standby [EN15502-2;EN15316-1-4]
P
stand-by
kW
0.112
0.574
0.694
0.127
Flue losses with burner off
%
0.1
Housing losses [Taverage=60°C]
%
0.35
0.40
0.40
0.50
MAX condensation
l/h
0.8
1.6
2.2
3.5
Flue gas emissions
Carbon monoxide - CO - [3% of 0
2
] - [80/60°C] - Pn³
78ppm-97mg/kWh 76ppm-95mg/kWh 73ppm-91mg/kWh 71ppm-89mg/kWh
Carbon monoxide - CO - [0% of 0
2
]
4
ppm
34
30
44
27
Nitrogen oxides - NOx - [Hi] [0% of 0
2
]
4
22ppm-39mg/kWh 15ppm-27mg/kWh 34ppm-61mg/kWh 24ppm-43mg/kWh
Nitrogen oxides - NOx - [Hs] [0% of 0
2
]
4
20ppm-35mg/kWh 14ppm-24mg/kWh 32ppm-56mg/kWh 22ppm-39mg/kWh
Fumes temperature
°C
75
48
75
40
75
40
83
35
Pressure available at the flue
Pa
120
100
150
90
Electrical Characteristics
Supply voltage
V
230V-50 Hz single-phase
Rated power
W
101
68
152
54
180
64
235
95
Electric power of auxiliary components (excluding
circulator)
elmax
W
48
12
88
10
104
12
110
13
Electric power of auxiliary components at 30% of load
(excluding circulator)
elmin
W
14
14
17
18
Electric power of auxiliary components in standby
P
SB
W
5
Operating Temperatures
°C
-15°C to +50°C
Protection Rating
IP
IPX5D
Hydraulic connections
Maximum working pressure
PMS
bar
3.0
Boiler water content
l
5.0
6.3
7.0
10.0
Delivery/return connections - UNI ISO 7/1 -
Ø
G 3/4" M
G 1" M
G 1 1/2" M
Gas connection
Ø
G 3/4" M
Operating weight (water included)
kg
35
45
47
90
Weight with packaging
kg
40
43
45
106