AQUAKOND AKY
CONDENSING BOILER
12
code HC0048.10GB ed.B-1811
AKY
Flow rate curve - boiler available head
For its proper operation, AquaKond system requires the following water flow rates through the boiler:
•
32 flow rate within 900 and 1,300 l/h;
•
34 flow rate within 1,000 and 1,400 l/h;
•
50 flow rate within 1,600 and 2,000 l/h;
•
70 flow rate within 1,800 and 2,000 l/h;
•
100 flow rate within 3,100 and 3,400 l/h.
The boiler can operate correctly even with lower water flow rates; in this case, to reach the maximum heat output, increase hot
water delivery temperature, thereby increasing its thermal difference.