1 0
To access the programming mode enter the engineer access code (factory default
[1][2][3][4][4][3][2][1])
and press the Select button. The engineer access code is a character sequence from
[1]
t
[8]
with length
from 1 to 10 characters.
Level 4 – maintenance
The level involves the special auxiliary software (used at the manufacturing company or service centers).
5.2.3 Programming features
Configurating and setting of the following objects can be programmed:
AL
-
AL operation algorithm (with verification, without verification, 2 detectors’ trigger);
-
AL type (Active, Passive, Combined, Combined - passive detector trigger priority, Combined
– active detector trigger priority);
-
Fixation of basic current of each AL (AL current in standby mode);
-
Time of AL reset in case of verification or manual reset (a value of the range: 5 sec, 10 sec, 15
sec, 20 sec, 25 sec, 30 sec, 35 sec, 40 sec);
-
Time of AL verification (a value of the range: 10 sec, 20 sec, 30 sec, 40 sec, 60 sec, 120 sec,
180 sec, 240 sec);
-
Current growth threshold to identify active detector trigger (from 1 to 8 mA with 1 mA pitch);
-
Current decrease threshold to identify passive detector trigger (from 0,8 to 3,6 mA with 0,4
mA pitch);
OUT1 and OUT2 high current programmable outputs (to 300 mA)
-
functional purpose of Out1, Out2 (power output of 4-wire AL, output of auxiliary
programmable light (sound) alarm or power output of auxiliary device (+12V));
-
modes of Out1 and Out2 (5 options); The setting determines the status of outputs in active and
passive state;
-
activation time of Out1 and Out2 in the mode of auxiliary adjustable light or sound alarm (1
sec, 5 sec, 10 sec, 30 sec, 1 min, 3 min, 10 min, 30 min, 1 h, 3 h, 10 h, not limited);
-
Activation conditions of Out1, Out2 in the mode of auxiliary adjustable light or sound alarm
(response to FIRE status in AL, response to FAULT status in AL, response to general FAULT
status, response to “Detector trigger in AL” status, response to ALARM status);
-
AL mask, participating in logical condition of output activation on AND/OR:
-
Types of load control of Out1, Out2 (S/C alone, O/C alone, S/C&O/C, without load control);
-
Time of transitional processes at switching of outputs is the time of non-response to faults (150
msec, 200 msec, 250 sec, 300 msec);
-
Setting of frequency of output’s pulse mode at appropriate mode setting (0,5 Hz, 1 Hz).
K1…K4 low current programmable outputs (to 40 mA)
-
modes of K1…K4 outputs (5 options). This setting defines statuses of outputs in active and
passive state;
-
time of active state of K1…K4 outputs in the mode of auxiliary adjustable light and sound
alarm (1 sec, 5 sec, 10 sec, 30 sec, 1 min, 3 min, 10 min, 30 min, 1 h, 3 h, 10 h, not limited);
-
activation conditions of outputs: (response to FIRE status in AL, response to FAULT status in
AL, response to general FAULT status, response to “Detector trigger in AL” status, response
to ALARM status);
-
setting of AL participating in condition of output activation on AND/OR;
-
setting of load control types of the outputs (S/C alone, O/C alone, S/C&O/C, without load
control);
-
time of transitional processes at switching of outputs is the time of non-response to faults (150
msec, 200 msec, 250 sec, 300 msec);
-
setting of frequency of output’s pulse mode at appropriate mode setting (0,5 Hz, 1 Hz).
Light and sound alarms (Light and Sound outputs)
modes of sound and light alarms. (statuses in active and passive state; steady or pulse modes);
time of active state (1 sec, 5 sec, 10 sec, 30 sec, 1 min, 3 min, 10 min, 30 min, 1 h, 3 h, 10 h, not limited);
load control type of the outputs (S/C alone, O/C alone, S/C&O/C, without load control);