2 0
3,6 m
11
No feedback (
by default
)
1
8
24
Feedback for
intellectual
detectors in AL
12
To make power outage in AL every second for 20
msec in Fire mode
8.5 Section 2. Configuration of «Out1» «Out2» outputs
Table 8.2
Section
Ouput’s
number
Out n
Parameter’s code
and name
Parameter’s
value
Description
Output’s functional purpose
11
4-wire AL power output
(
by default
)
12
Auxiliary adjustable
light
alarm output
13
Auxiliary adjustable
sound
alarm output
14
Output is not used
2
n
1
15
Output of 12V non-commutated power of
auxiliary devices
Mode of output (if OutN – output to sounder)
11
disabled – passive state, continuous
enabled – active state (
by default
)
12
enabled– passive state,
disabled – active state
13
disabled – passive state,
pulse mode – active state
14
enabled– passive state,
pulse mode – active state
2
n
2
15
enabled– passive state,
pulse mode – active state,
and disabled , if one of AL included to output
activation condition is disabled by authorized
user.
Output’s activation time
(if OutN – output to detector)
11
1 sec
12
5 sec
13
10 sec
14
30 sec
21
1 min
22
3 min (
by default
)
23
10 min
24
30 min
31
1 h
32
3 h
33
10 h
2
n
3
34
not limited (till activation condition reset)
2
n
4
Output’s activation condition
(Note 8.5.1)
2
n
5
Mask of AL, involved to output’s activation condition
(Note 8.5.2)
Type of output’s load control
2
n
6
11
Control S/C alone (
by default
)