2 5
8.7 Section 4. Configuration of sounders.
N = 1- light alarm («Light» output)
N = 2 – sound alarm («Sound» output)
Table 8.4
Section
Output’s
number
Code and
name of
parameter
Parameter
value
Description
Sounder mode
11
Disabled – passive state, enabled – active state
12
Enabled – passive state, disabled – active state
(parameter’s value only for light alarm)
13
disabled – passive state, pulsing mode – active state
(
by default).
14
enabled – passive state, pulsing mode in active state
(parameter’s value only for light alarm)
4
N
2
21
Enabled – passive state, pulsing mode in active state
and disabled if one of AL is disabled by authorized
user. (
parameter’s value only for light alarm
)
Active state’s time
11
1 sec
12
5 sec
13
10 sec
14
30 sec
21
1 min
22
3 min (
by default
)
23
10 min
24
30 min
31
1 h
32
3 h
33
10 h
4
N
3
34
Not limited (till resetting the activation condition)
Type of load control of the output
11
Control only «S/C»
12
Control only « /C» (1-10 kohm resisitor is required to
be installed) parallel to load.
13
Control «S/C» and «O/C» (
by default
)
4
N
6
14
No control.
Time of transition processes at output’s switching
11
150 msec (
by default
)
12
200 msec
13
250 msec
4
N
7
14
300 msec
Frequency of pulsing mode in active state of the output
11
0,5 Hz
4
N
8
12
1 Hz (
by default
)
The panel allows to set one of 2 modes of light-sound alarm output («
L/S
» output): pulsing or steady.
To view and change the mode of the light-sound alarm it is required to enter using number buttons:
[2][1][1]
As a result the red indicator
[1]
turns on
,
and the mode of the light-sound alarm’s operation is defined
by the yellow indicator light
[1]
:
Steady light – non-stop mode;