1 5
7.5.1 Connect the storage battery as it is shown on the figure in Appendix 3. Connect the black wire
to the minus terminal, the red wire - with the plus terminal of SB.
Note. When connecting the storage battery the polarity should be kept. Incorrect polarity of
connection leads to the «Fuse1 1.0A» failure.
7.6 Authorized user mode
7.6.1 General overview
To access the panel’s controls enter the access code. There are 8 programmable access codes for each of
8 users and one programmable engineer’s access code.
Each user can have rights to control one or several AL, that allows to delimit responsibility for guarded
premises.
To access the mode the access code of one of 8 users should be entered. The access code is entered with
[1]
..
[8]
buttons in Zone group and confirmed by pressing the Select button. After that if the entered code is
correct, the Authorized user indicator turns on and the panel goes into the mode. To Exit the authorized user
mode press the Cancel button 3 times or automatically if none of the buttons was pressed within 30 sec.
The following functions are available in the mode:
– disabling or enabling of zones;
– resetting of Fire, Fault, Alarm modes;
– resetting of all AL (temporal turning off of power for 5-6 sec. of all 2-wire and 4-wire AL);
– disabling (muting) or enabling (restoring) of output signals Light and Sound;
– disabling (muting) or enabling (restoring)of Fire output signal;
– disabling (muting) or enabling (restoring) of Fault output signal;
– testing the light indicators and internal sounder for proper operation.
7.6.2 AL disablement/enablement
To disable a switched on AL in the authorized user mode press for 2-3 sec the corresponding zone
button (
[1]
..
[8]
). While the button is being pressed the internal sounder steadily sounds. The button should
be kept pressed until the sound signal is silenced. When the sound has been muted the AL becomes disabled
and the yellow light indicator of the AL and the Disabled general indicator switch on. As a result of the
disablement the AL activates (the Fault output gets disabled).
After the panel has been deenergized and then energized again the status of AL disablement retains.
Disablement and enablement of an AL can be made by pressing for 2-3 sec the button of corresponding
zone. The internal sounder sounds while the button is being pressed. The button should be kept pressed
until the sound signal is silenced. When the sound has been muted the AL gets enabled.
Disablement/enablement of an AL by a user is impossible if the user has not rights to control the AL.
The user authorities can be set in the programming mode (see p. 8.7).
7.6.3 Resetting zones, Fire, Fault and Alarm modes
Resetting of the modes can made in the authorized user mode by pressing for 2-3 sec the Reset button.
In the same way as when the AL is disabled/enabled the internal sounder sounds while the button is being
pressed. The button should be kept pressed until the sound signal is silenced.
7.6.4 Disablement of light and sound alarms (Light and Sound outputs)
To disable light and sound alarms in the authorized user mode pressing the
[1]
button while keeping
pressed the Select button. Pressing the
[1]
button again while keeping pressed the Select button allows to
enable the light and sound alarms when Fire or Alarm condition occur.
Disablement of light and sound alarm is indicated by the steady light of the yellow general indicator
Disabled and Sounder indicator from the Disabled group.
7.6.5 Disablement of Fire output signal (Fire output)
Disablement of the Fire output signal («
Fire
») occurs automatically when resetting the Fire mode.
For temporal disablement of the signal in the Fire mode the
[2]
button should be pressed in the authorized