Software functions
7-15
7.1.2.4 Control command
Control command is carried out on B2G78-E1.
Modbus/TCP address
Value
Description
Details
Memory address Offset address
41204 1203
0 Invalid
-
1
Remote reset
Resets the B2G78-E1 by remote operation.
Provides the same effect as resetting the
power.
2 Automatic
address
recognition
Carries out automatic address recognition.
Refer to SET switch of "Switch functions" for
details.
3 Address
redundancy check
Carries out address redundancy check for
the currently connected device.
Even if automatic address recognition is not
carried out, only the redundancy check is
carried out.
4 Parameter
access
command
Applies the parameter access method and
parameter access target to ASLINK, and
carries out ASLINK parameter operation for
one unit.
5 Parameter
access
collective reading
command
Reads parameters of all units (only
recognized IDs; not carried out for
disconnection IDs, redundant IDs, and
default setting ID (255)).
6 Parameter
access
collective writing
command
Writes parameters of all units (only
recognized IDs; not carried out for
disconnection IDs, redundant IDs, and
default setting ID (255)).