AnyWireASLINK
6-7
6.6 Transmission cable type and precautions
General-purpose cabtyre cables, twisted pair cables and dedicated flat cables, and similar cables can be
used for the transmission cable.
Use the following for electric wires.
General-purpose
two-wire/four-wire cable (VCTF, VCF 0.75 to 1.25mm
2
, rated temperature 70ºC)
General-purpose electric wire (0.75 to 1.25mm
2
, rated temperature 70ºC)
Dedicated flat cable (0.75mm
2
, 1.25mm
2
, rated temperature 90ºC)
Shielded cable
Since AnyWire has high noise resistance, it is unnecessary to use shielded cable.
Please note that if the shielded cable shielding is not properly grounded, it may result in
problems during use.
Transmission cable
Be careful to prevent the voltage from dropping below the lower limit of the allowable voltage
range due to voltage drop caused by the cable.
Dropping below the lower limit may result in malfunction.
Install a local power supply if the voltage drops significantly.
Do not connect soldered wire directly to a terminal. Looseness may result in contact failure.
CAUTION
CAUTION