Software functions
7-10
7.1.1.11 R/O parameter storage area (30x128)
Blocks in which parameters and statuses that were read from a slave are stored are arranged in ID
ascending order.
Modbus/TCP address
Memory
address
Offset
address
31891
1890
Parameter area 1 (30 words)
The parameter area of each ID
has 30 words and can store a
maximum 128 pieces of
information.
The header of the 30 words
indicates the ID, and data is
arranged in 30-word units in ID
ascending order.
It is necessary to perform
automatic address recognition
again when a slave unit is added
or the ID of a unit is changed.
・
・
・
・
・
・
31920
1919
31921
1920
Parameter area 2 (30 words)
・
・
・
・
・
・
31950
1949
・
・
・
・
・
・
・
・
・
35701
5700
Parameter area 128 (30 words)
・
・
・
・
・
・
35730
5729
The content of each parameter area block is as follows.
Offset
Parameter name
R/W
Classification
0
Slave unit ID
R/W
ASLINK access not required, referred
from internal memory
1
Device parameter 1
R/W
Interrupt access, initial access
2
Device parameter 2
R/W
Interrupt access, initial access
3
Device parameter 3
R/W
Interrupt access, initial access
4
Device parameter 4
R/W
Interrupt access, initial access
:
:
:
:
:
:
:
:
15
Device parameter 15
R/W
Interrupt access, initial access
16
Device parameter 16
R/W
Interrupt access, initial access
17
Device parameter 17
R/W
Interrupt access, initial access
18
Device parameter 18
R/W
Interrupt access, initial access
19
Device parameter 19
R/W
Interrupt access, initial access
20 Status
details
R/O
Cyclic access
21 Sensing
level
R/O
Cyclic access
22 System
reserved
23 System
reserved
24 System
reserved
25 System
reserved
26 System
reserved
27 System
reserved
28 System
reserved
29 System
reserved