System
F3
Fault on sensor for cur-
rent or voltage�
Replace circuit board on outdoor unit�
F4
Fault on compressor
drive, fault on overload
protection, or overload
protection has tripped�
1� Check that sensor is correctly connected and rectify if
necessary�
2� Replace sensor�
3� Replace circuit board on outdoor unit�
F5
ult on indoor unit
EEPROM�
1� Check that EEPROM is correctly connected and rectify if neces-
sary�
2� Replace indoor unit EEPROM�
F6
Battery temperature
in indoor unit too high
during heating�
1� Check water flow in unit�
2� Reduce the set point water temperature�
Conduit temperature in
outdoor unit too high
during cooling�
1� Check water flow in unit�
2� Increase the set point water temperature�
Overload protection has
tripped�
1� Check water flow in unit�
2� Use a set point temperature closer to the ambient temp�
F7
Voltage too high or too
low�
1� Check supply voltage�
2� Replace circuit board on outdoor unit�
F8*
Defective pressure switch�
1� Check system pressure�
2� Replace pressure switch�
F9
Fault on outdoor unit
EEPROM�
1� Check that EEPROM is correctly connected and rectify if
necessary�
2� Replace outdoor unit EEPROM�
Fb
Fault on outdoor tempe-
rature sensor�
1� Check that the sensor is correctly connected, and rectify if
necessary�
2� Check for short circuit or wire fault between the wired control
unit and indoor unit circuit board�
3� Check for resistance deviation on temperature sesnsor�
Fault on sensor for
conduit temperature in
outdoor unit�
Fault on sensor for
compressor outlet tem-
perature�
Fd
Temperature protection
for system has tripped
as a result of high/low
ambient temperature�
1� Check sensor for ambient temperature�
2� Check if ambient temperature is outside permitted operating
temperature (lower than -1 or higher than 65°C during cooling,
lower than -25 or higher than 45°C during heating)�
Fc*
Over/underpressure
protection for system has
tripped
1� Check with multimeter if pressure sensor has a wire fault or is
short circuited� If so, replace pressure sensor�
2� Check water flow in unit�
Fe
Reserved error code�
FF
Fault on indoor unit wa-
ter pump or flow switch�
1� Check water flow in water pump�
2� Check connection of flow switch� If there is enough water
flowing in the system, check whether the flow switch works�
Replace flow switch, if necessary�
* Difference between F8 and Fc:
Summary of Contents for 416-108
Page 11: ...SE 11 TEKNISKA DATA...
Page 13: ...SE 13 DELAR Inomhusenhet Utsida Ovansida Inv ndigt...
Page 14: ...SE 14 Utomhusenhet 1 Luftinlopp 2 Luftutlopp 3 R rsats med snabbkoppling...
Page 15: ...SE 15 M TT Inomhusenhet Enhet mm...
Page 16: ...SE 16 Utomhusenhet V tsker r YD 6 35 1 4 Gasr r YD 12 7 1 2 Luftinlopp Luftinlopp...
Page 64: ...NO 64 TEKNISKE DATA...
Page 66: ...NO 66 DELER Innedel Utside Overside Innside...
Page 67: ...NO 67 Utedel 1 Luftinntak 2 Luftutl p 3 R rsett med hurtigkobling...
Page 68: ...NO 68 M L Innedel Del mm...
Page 69: ...NO 69 Utedel V sker r YD 6 35 1 4 Gassr r YD 12 7 1 2 Luftinntak Luftinntak...
Page 113: ...PL 113 DANE TECHNICZNE...
Page 115: ...PL 115 CZ CI Jednostka wewn trzna Strona zewn trzna G ra Wn trze...
Page 116: ...PL 116...
Page 118: ...PL 118 Jednostka mm...
Page 119: ...PL 119 Jednostka zewn trzna Rura cieczowa r zew 6 35 1 4 Rura gazowa r zew 12 7 1 2 Wlot Wlot...
Page 167: ...EN 167 TECHNICAL DATA...
Page 169: ...EN 169 PARTS Indoor unit Outside Top Internal...
Page 170: ...EN 170 Outdoor unit 1 Air inlet 2 Air outlet 3 Pipe set with quick coupling...
Page 171: ...EN 171 DIMENSIONS Indoor unit Unit mm...
Page 172: ...EN 172 Outdoor unit Fluid pipe OD 6 35 1 4 Gas pipe OD 12 7 1 2 Air inlet Air inlet...