10
In case that some ArcDot has been changed, the same address as had original ArcDot is assigned to it by the
ArcPixel Power-CE.
It is very important to save ArcDots configuration at every change of an ArcDot
.
(Menu "Dots" -> "Store Config"),
Max. cable length between ArcPixel Power-CE and the last connected ArcDot module should not be exceeded:
100m @ 25 ArcDots per LED output
or
65 m @ 35 ArcDots per LED output
.
Only one ArcDot can be connected to the T-connector.
Note: If DMX is used for control of the ArcPixel Power-CE, the LED outputs 1-3 may be used only.
(In this case, one UART from four available UARTs is used for DMX input and remaining three UARTs can be
used for LED outputs only. LED output load is the same as in a case of the control by Artnet - max 35 LED
modules per LED output, max. 100 modules per ArcPixel Power-CE).
Every ArcDot line has to be terminated with the passive terminator!
Note: the same rules as for the ArcDots-CE go for the ArcSource Outdoor 4MC Pixels-CE and Arc-
DotFlashes-CE with the following exception for the ArcDotFlashes-CE: If no DMX signal is present at
ArcPixel Power-CE, the ArcDotFlash modules flash randomly (22-28 flashes per minute).
The Robe Media Server allows you to choose two modes of ArcDots connection: Fixed-wiring mode and Picture
mode. For detailed description see the user manual of the Robin Media Server.
Number of needed ferrites:
- at each ArcDot output: 1
- total for installation: 3
Three LED outputs
can be used only