Engineer
34
MAXXfl o EVO
Phase
No:
Phase
display
reference
code
Phase
Phase description
Explanation
1
TNB
Homerun
Permitted afterburn
time
Not relevant for the MAXXfl o EVO
2
TLO
Homerun
Permitted time with air
pressure switch closed
or fan speed
Time after post purge when the air fl ap is still open as the fan
speed runs down
3
TNN
Homerun
Permitted time with fan
speed
Time after post purge when the fan is permitted to run on
4
STY
Standby
No demand
No heat demand, burner is not active
5
STV
Standby
Start prevention
Burner held until a temporary condition has been removed (e.g.
B2 sensor disconnected)
6
THL1
Startup
Fan ramp-up time to
ignition speed
Maximum fan ramp-up time for fan to reach pre-purge speed
7
THL1A
Startup
Fan ramp-up time to
ignition speed
Maximum fan ramp-up time for fan to reach ignition speed
8
TV
Startup
Pre-purging
Fan pre-purging phase
9
TBRE
Startup
Fan adjustment
Maximum time required to reach ignition level after pre-purging
10
TW1
Startup
Waiting time
Maximum waiting time until the following functions complete:
- Internal safety tests
- Fan speed adjustment to ignition load
11
TW2
Startup
Waiting time
Fan speed adjustment to ignition load
12
TVZ
Startup
Pre-ignition phase
Time before ignition (minimum 0.2 seconds)
13
TSA1
Safety time 1st safety time
First part of safety time with spark on and gas valve open
14
TSA2
Safety time 2nd safety time
Second part of safety time with spark off and gas valve open
15
TI
Operation
Interval
Stabilisation of fl ame (5 seconds)
16
MOD
Operation
Control mode
Burner is modulating normally - Main phase of operation
17
THL2
Shutdown
Post purging
Post purging at last operating fan speed - Demand has been
turned off , gas valve will be closed
18
THL2A
Shutdown
Post purging
Post purging at pre-purge fan speed - Demand has been turned
off , gas valve will be closed.
19
TN1
Shutdown
Post purging
Post purging at last operating fan speed - Demand has been
turned off , gas valve will be closed
20
SAF
Error
Boiler error state
Certain types of error can force the heater control to jump to this
phase and all safety related outputs are deactivated. When the
condition returns to normal, this phase will be skipped and the
control will restart. This will avoid lockout and the need to reset.
21
STOE
Error
Boiler error state
If the heater controls detect a system error that would drive the
heater into an unsafe state (i.e. lockout), the heater controls will
jump to this phase. Only an applied reset can resume operation.
22
TNA
Shutdown
Post purging at pre-
purge speed
Last phase of fan post purge before the boiler controls go to
standby phase.
23
KT
Standby
Start prevention
Temporary start prevention condition becomes a permanent con-
dition after a period of time has elapsed.
24
TN2
Shutdown
Interruptable post
purging
Interruptable post purging at last fan operation speed. If there is a
new heat demand during the post purge period, post purging can
immediately be interrupted.
4.3 ERROR HISTORY - BURNER CONTROL PHASE