Engineer
40
MAXXfl o EVO
4.5 COMPLETE PARAMETER LIST TABLE (CONTINUED)
PARAMETER
DESCRIPTION
FACTORY
DEFAULT
NOTES
DHW storage tank (continued)
5101
Pump speed minimum
DHW
EVO 30 = 44%
EVO 60 = 59%
EVO 90 = 58%
EVO 120 = 67%
Used to increase the minimum pump speed whilst in DHW
heating.
Increasing minimum pump speed decreases the DeltaT of the
water being heated
General functions (used for controlling the optional BUFFER SS300-10
5570
Temp diff on dT contr 1
2.0
OI
C
If the temperature diff erence between the BUFFER SS300-10
tank and the MAXXfl o EVO tank is greater than this value,
K21 transfer pump output will be turned on
5571
Temp diff off dT contr 1
1.0
o
C
If the temperature diff erence between the BUFFER SS300-10
tank and the MAXXfl o EVO tank is less than this value, K21
transfer pump output will be turned off
5572
On temp min dT contr 1
0
o
C
Not used
5573
Sensor 1 dT contr 1
DHW sensor B3 Sensor used for delta T comparison for K21 transfer pump
activation
5574
Sensor 2 dT contr 1
Special temper-
ature sensor 1
Sensor used for delta T comparison for K21 transfer pump
activation
5575
On time min dT contr 1
30s
Represents the minimum time that K21 will be activated even
if parameter 5571 conditions are met
5577
Pump/valve kick K21
On
Pump output on
5580
Temp diff on dT contr 2
2.0
OI
C
If the temperature diff erence between the BUFFER SS300-10
tank and the MAXXfl o EVO tank is greater than this value,
K22 transfer pump output will be turned on
5581
Temp diff off dT contr 2
1.0
o
C
If the temperature diff erence between the BUFFER SS300-10
tank and the MAXXfl o EVO tank is less than this value, K22
transfer pump output will be turned off
5582
On temp min dT contr 2
0
o
C
Not used
5583
Sensor 1 dT contr 2
DHW sensor B3 Sensor used for delta T comparison for K22 transfer pump
activation
5584
Sensor 2 dT contr 2
Special temper-
ature sensor 1
Sensor used for delta T comparison for K22 transfer pump
activation
5585
On time min dT contr 2
30s
Represents the minimum time that K22 will be activated even
if parameter 5581 conditions are met
5587
Pump/valve kick K22
On
Pump output on
Confi guration
6020
Function extension
module 1
None
Defi nes purpose of AGU2.550 clip-in extension module.
When using an extension module with the MAXXfl o EVO this
setting should be changed to “Multifunctional”
6024
Function input of EX21
module 1
None
Defi nes purpose of AGU2.600 clip-in extension module.
6030
Relay output QX21
module 1
None
Defi nes the purpose of the output QX21 on a AGU2.550 clip-
in extension module
6031
Relay output QX22
module 1
None
Defi nes the purpose of the output QX22 on a AGU2.550 clip-
in extension module
6032
Relay output QX23
module 1
None
Defi nes the purpose of the output QX23 on a AGU2.550 clip-
in extension module
6040
Sensor input BX21
module 1
None
Defi nes the purpose of the sensor input BX21 on a AGU2.550
clip-in extension module
6041
Sensor input BX22
module 1
None
Defi nes the purpose of the sensor input BX21 on a AGU2.550
clip-in extension module
6031
Relay output QX22
module 1
None
Defi nes the purpose of the output QX22 on a AGU2.550 clip-
in extension module