MAXXfl o EVO
4.5 COMPLETE PARAMETER LIST TABLE (CONTINUED)
PARAMETER DESCRIPTION
FACTORY
DEFAULT
NOTES
Burner control
9500
Prepurge time
15s
The length of time to purge the fl ue system on startup of
the burner can be increased up to 51 seconds if required
9501
Prepurge time min
15s
Minimum possible pre-purge time, beyond which it is not
possible to reduce parameter 9500
9512
Required speed at ignition
30kW = 2500rpm
60kW = 3500rpm
90kW = 2500rpm
120kW = 3500rpm
Fan speed required for ignition
9513
Required speed ignition
max
30kW = 2790rpm
60kW = 3990rpm
90kW = 3510rpm
120kW = 3990rpm
Maximum limitation of 9512
9524
Required speed Low Fire
30kW = 1900rpm
60kW = 1950rpm
90kW = 1900rpm
120kW = 1950rpm
Fan speed required at minimum burner modulation
9525
Required speed Low Fire
minimum
30kW = 1900rpm
60kW = 1950rpm
90kW = 1900rpm
120kW = 1950rpm
Minimum limitation of 9524
9529
Required speed High Fire
30kW = 4650rpm
60kW = 6650rpm
90kW = 5950rpm
120kW = 6650rpm
Fan speed required at maximum burner modulation
9530
Required speed High Fire
maximum
30kW = 4650rpm
60kW = 6650rpm
90kW = 5950rpm
120kW = 6650rpm
Maximum limitation of 9529
9540
Postpurge time
15s
Number of seconds that the fan will continue to operate
after the gas valve has closed
9542
Postpurge time minimum
15s
Minimum limitation of 9540
9650
Chimney drying
Off
Function can be used to dry out the lining of a chimney or
used to check the operation of a burner fan without fi ring
the burner with gas (only the fan runs in this mode). Only
active when the heater is in standby and can be interruopt-
ed at any time with a request for heat
9651
Required speed chimney
drying
500rprm
Pre-determined speed for chimney drying function. A mini-
mum fan speed of 1500rpm is recommended
9652
Duration chimney drying
10 minutes
Duration of chimney drying function (maximum 1440 min-
utes)