Edition 3
Rev G
Section 3
3-9
3.8.2 NEW CHART PRINTING REQUIREMENTS
The following ACTION ON NEW CHART options are provided:
NONE - JUST CONTINUE
PRINT RANGE LIST
PRINT SCALES
The following example illustrates the format used if PRINT RANGE LIST has been configured. This method
would be selected to reduce the time between chart installation and initial trend recording. This Range List
corresponds to the example found at the end of this section.
Line
Description
Color
1
FLOW #1
Recorder Tag
Black
2
0/400 GPM
Span, Units
Black
3
TEMP #1
Recorder Tag
Blue
4
20/120 *F NL
Span, Units
Blue
5
PH #1
Recorder Tag
Green
6
0/14 PH NL
Span, Units
Green
7
ALARM #1
Recorder Tag
Red
8
0/1 NL
Span, Units
Red
If the scale is other than a simple 0 to 100% of chart with one zone, "NL" will follow the units to indicate non
linear.
If PRINT SCALES has been configured, the instrument will proceed to print, as needed per the chart format, time
lines, scale lines, scale values, units and recorder tag for each recording pen which is configured. The time, date,
and chart tag will not be printed during this process. The chart will be advanced to the correct position for the
next time line after the completion of printing for each recording pen.
Upon completion of PRINT RANGE LIST or PRINT SCALES, if configured, the instrument is ready to begin
trending. Trending will not begin if the instrument status has been set to OFF or the chart has been stopped.
When the instrument first begins trending after a new chart has been installed, it will print, as needed per the
chart format, time lines, scale lines, scale values, units, and recorder tag for each recording pen until it reaches
the position corresponding to the current time. If the instrument status has not been set to off and the chart
has not been stopped by other than the chart being full, historical trend data will also be included. The
time, date, and chart tag will be printed during this process. At this point, the instrument will begin the normal
recording process and marks the chart on the outer ring with an arrow("
¨
") to indicate where the trend began.
3.8.3 EXAMPLE CHART
Figure 3-2 (page 3-12) illustrates the typical data presentation for a 12" chart. The "recorder" trends are referred
to by number in this illustration for black and white reproduction.
Refer to Table 3-1 (page 3-10) and Table 3-2 (page 3-11) for the corresponding recorder configuration/program-
ming data. For this example, the instrument has four inputs as follows:
1
Raw Flow Value
2
Temperature
3
Pressure
4
pH
The value recorded on Pen 1 is a derived value; flow corrected for temperature and pressure. The derived value
is also converted to a process value for alarming.
(Continued on next page)
Summary of Contents for AV-9000
Page 2: ......
Page 4: ......
Page 22: ......
Page 290: ...Appendix A Edition 3 Rev G A 2 FIGURE A 2 MOTHER BOARD J5 J6 J4 J7 J1 J3...
Page 293: ...Edition 3 Rev G Appendix A A 5 FIGURE A 5 MOTOR DRIVER BOARD J4B J5 J6 J1 J7 J4A J3 J2...
Page 295: ...Edition 3 Rev G Appendix A A 7 FIGURE A 7 TRANSMITTER POWER SUPPLY BOARD J3 TB2 TB1 TB3 TB4...