Section 13
Edition 3
Rev G
13-34
6. Press the
to advance to the next parameter, OUTPUT 1 SHIFT.
Cx OUT 1 SHIFT
0 units
Note: Units correspond to Units
configured in Process Variables.
Selections
0 to 999999
(decimal position=0)
0 to 9.9999
(decimal position=4)
7. Press the
to advance to the next parameter, OUTPUT 2 SHIFT (only if Output 2 is used).
Cx OUT 2 SHIFT
0 units
Note: Units correspond to Units
configured in Process Variables.
Selections
0 to 999999
(decimal position=0)
0 to 9.9999
(decimal position=4)
OUTPUT SHIFT represents an offset of the on-off actuation points or proportional band relative to the normal
position. For example, if two on-off outputs are being used, one for heating and one for cooling, and a deadband
of 2
∞
is desired between the two, set OUT 1 SHIFT to -1 and set OUT 2 SHIFT to +1.
Press the
to change, then
or
to desired number, then press the
.
Press the
to change, then
or
to desired number, then press the
.