-6-
5. CH-41BZ CHAMPION SERIES PIPING INSTALLATION
DOMESTIC WATER PIPING
1. Thread the included
3
/
4
” brass tee onto the pipe marked
COLD WATER.
2. Screw the
3
/
4
” drain valve into the opposite end of the brass
tee.
3. Connect the cold water supply to the remaining port on the
brass tee.
4. Temporarily attach the top tee fitting (with o-ring face seal)
to the union nut on top of the tank. Test fit the piping near
the tee before soldering. Remove the tee before soldering
connections to avoid damage to the top o-ring seal or
plastic liner.
Note: Do not solder piping within 24 inches of the top
tee fitting while attached to the tank.
5. Make an 8-inch “heat trap” as shown in the diagram. This
will reduce standby losses from heat migrating up the
piping. Continue this line to the domestic hot water system.
6. Install the included T&P relief valve on the top port of the
top tee connection. Plumb a blowdown tube to within 6
inches of a floor drain or as directed by plumbing code.
Note: No valve is to be placed between the T&P relief
valve and the tank.
Note: Valves for reducing point of use temperature
by mixing cold and hot water are available. Consult a
licensed plumber or the local plumbing authority.
7. When all domestic water piping is complete, open the cold
water supply and allow some water to enter the tank. Look
and listen for signs of leaks and repair as necessary before
continuing.
Note: If a water heater is installed in a closed water
supply system, such as one having a back-flow
preventer in the cold water supply line, means shall
be provided to control thermal expansion. Contact the
water supplier or local plumbing inspector on how to
control this situation.
BOILER PIPING
1. Plumb the circulator or zone valve on the BOILER SUPPLY
line. If using a separate circulator, the pump flange
can be mounted directly to the threaded pipe marked
BOILER SUPPLY. Alternately, the circulator can be placed
anywhere on the boiler supply line.
2. Pipe the BOILER RETURN connection to the boiler return
line.
Be sure the return line is NOT
plumbed to the suction side of
any heating circulators. This may require moving the
heating circulator off the boiler tapping on packaged
boilers. Failure to do so will result in overheating and
tank damage when the heating system is in operation.
3. Install a weighted flow check on the boiler return line. This
is not necessary on systems utilizing a zone valve to control
the BoilerMate
®
temperature.
4. After completing the boiler piping, slowly open the boiler fill
valve and pressurize the BoilerMate
®
loop. Check for leaks
and repair as necessary. Proceed to the appropriate wiring
section in this manual.
If installing on city water supply a
properly sized THERM-X-TROL
®
is
required with the BoilerMate
®
and should be installed as set
forth in the THERM-X-TROL
®
product installation manual.
LEFT SIDE . . . . . . . . . .1”
RIGHT SIDE. . . . . . . . .1”
TOP . . . . . . . . . . . . . . .9”
REAR . . . . . . . . . . . . . .1”
FLOOR. . . . . . . . . . . . .0”
FRONT. . . . . . . . . . . . .1”
Clearance From Combustible Surfaces
HOT WATER OUTLET
BOILER RETURN (Top Left)
BOILER SUPPLY (Top Right)
T&P RELIEF VALVE
COLD WATER INLET
(Bottom Center)
UNION NUT
LEFT . . . . . . . . . . . . .12”
RIGHT . . . . . . . . . . . .12”
FRONT . . . . . . . . . . .30”
HEAD ROOM. . . . . . . .9”
REAR . . . . . . . . . . . . . .1”
Recommended Clearance For Servicing