background image

-2-

1. TABLE OF CONTENTS

2.  Pre-Installation Checklist ..............................2

3.  Required Components and 
  Accessories Checklist ...................................3

4.  CH-41Z/CH80Z Piping Installation ...............4

5.  CH-41BZ Piping Installation ..........................6

6.  Wiring ............................................................8

7.  Startup Procedure For All Models ..............10

8.  Troubleshooting ..........................................11

9.  Replacement Parts ......................................12

10.  General Safety Information ........................13

2. PRE-INSTALLATION CHECKLIST

IMPORTANT STEPS AND DECISIONS REQUIRED BEFORE INSTALLATION

M

  THIS  PRODUCT  MUST  BE  INSTALLED  AND 

MAINTAINED  BY  A  LICENSED  PROFESSIONAL.  IN 

ADDITION  TO  THE  INSTRUCTIONS  IN  THIS  MANUAL, 

FOLLOW ALL APPLICABLE LOCAL AND STATE CODES 

OR IN THE ABSENCE OF SUCH CODES, THE CURRENT 

EDITIONS  OF  THE  NATIONAL  PLUMBING  CODE  AND 

THE NATIONAL ELECTRIC CODE.

M

  DRIP  PAN  AND  DRAIN:  This  appliance  should  not 

be  installed  in  an  area  where  leakage  of  the  tank  or 

connections can result in damage to the area adjacent 

to  the  appliance  or  to  lower  floors  of  the  structure. 

When  such  locations  cannot  be  avoided,  a  suitable 

drain pan, adequately drained and kept clear, must be 

installed under the appliance.

M

  CAUTION:  Determine  whether  your  water  is  corrosive 

or  acidic,  and  that  there  are  no  suspended  solids, 

toxic  or  other  substances  or  abnormally  high  chlorine 

levels  in  the  water  that  could  damage  or  affect  the 

BOILERMATE

®

 or the rest of your plumbing system.

USE 

GLYCOL 

ONLY 

WITH 

DOUBLE-WALLED HEAT EXCHANGER 

MODELS. Glycol is a hazardous substance. To avoid 

seepage  or  leakage  of  glycol  to  surfaces  where 

humans  or  animals  can  ingest  it,  use  glycol  only  in 

double-walled units, so that any leaks will most likely 

be released to the atmosphere.  However, a leak to a 

surface area may still occur, so any use of glycol must 

be monitored closely and humans and animals should 

be protected from contact with the unit.

Do  not  connect  the  BoilerMate

®

 

domestic  supply  with  baseboard 

or  other  space  heating  units  or  elements.  Any 

contaminants in the baseboard units will contaminate 

the potable water in the BoilerMate

®

 and also adversely 

affect its performance.

Select Circulator versus Zone Valve

  The  flow  of  hot  boiler  water  to  the  BoilerMate

®

 

can 

be  controlled  with  either  a  motorized  zone  valve  or  a 

circulator.

1. Separate  circulator.    The  recommended  way  to 

provide adequate flow through the BoilerMate

®

 heat 

exchanger  is  to  use  a  separate  dedicated  circulator 

with a minimum flow rate of 4 gpm.  This option may 

be used even though the heating system utilizes zone 

valves.

2. Zone valve (system flow of 4-8 gpm).  If a zone valve 

is to be used, a minimum flow rate of 4 gpm with all 

zones in use is required. A full-port zone valve should 

be used.

All installations require a low-water cut-off or automatic fill 

valve on your boiler system to reduce the risk of boiler water 

loss. 

In steam boiler installations a low-water cut-off which is also 

required by most codes.

Installation  of  a  vacuum  breaker  is  required  to  prevent 

damage  to  the  BoilerMate

®

  when  drained.  There  must 

be  no  valves  installed  between  the  vacuum  breaker  and 

BoilerMate

®

.

Summary of Contents for Champion CH-41BZ

Page 1: ...URRENT EDITIONS OF THE NATIONAL PLUMBING CODE AND NATIONAL ELECTRIC CODE AS APPLICABLE THIS IS THE SAFETY ALERT SYMBOL IT IS USED TO ALERT YOU TO POTENTIAL PERSONAL INJURY AND OTHER HAZARDS OBEY ALL SAFETY MESSAGES THAT FOLLOW THIS SYMBOL TO REDUCE THE RISK OF PERSONAL INJURY AS WELL AS PROPERTY DAMAGE The heat transfer medium must be water or other nontoxic fluid having a toxicity rating or class...

Page 2: ...seepage or leakage of glycol to surfaces where humans or animals can ingest it use glycol only in double walled units so that any leaks will most likely be released to the atmosphere However a leak to a surface area may still occur so any use of glycol must be monitored closely and humans and animals should be protected from contact with the unit Do not connect the BoilerMate domestic supply with ...

Page 3: ...iler system has an EXTROL or Radiant EXTROL expansion tank and the boiler temperatures are being changed resize the EXTROL or Radiant EXTROL expansion tank 20 15 10 5 0 0 2 4 Flow GPM Pressure Drop ft 6 8 MODEL OPTION CIRCULATOR ZONE VALVE SHUTOFF VALVE VACUUM BREAKER RELIEF VALVE THERMAL EXPASION TANK DRAIN CH 41 CH 41 CH 80 Z BZ Z 4GPM If Circulator not used 3 4 Full Port or 1 STD 4 1 Included R...

Page 4: ...e T P relief valve and the tank Note Valves for reducing point of use temperature by mixing cold and hot water are available Consult a licensed plumber or the local plumbing authority BOILER PIPING 1 Plumb the circulator or zone valve onto the BOILER SUPPLY fitting 2 Pipe the BOILER RETURN connection to the boiler return fitting Be sure the return line is NOT plumbed to the suction side of any hea...

Page 5: ... 5 PIPING USING DEDICATED CIRCULATOR PUMP RECOMMENDED PIPING USING ZONE VALVE WITH EXISTING HEATING SYSTEM CIRCULATOR ...

Page 6: ...ch as one having a back flow preventer in the cold water supply line means shall be provided to control thermal expansion Contact the water supplier or local plumbing inspector on how to control this situation BOILER PIPING 1 Plumb the circulator or zone valve on the BOILER SUPPLY line If using a separate circulator the pump flange can be mounted directly to the threaded pipe marked BOILER SUPPLY ...

Page 7: ... 7 CH 41BZ PIPING USING SEPARATE CIRCULATOR PUMP RECOMMENDED PIPING USING ZONE VALVE WITH EXISTING HEATING SYSTEM CIRCULATOR ...

Page 8: ...conduit metal clad cable or raceways Power Limited Circuit Cable need not be provided with the protection specified above if it is securely fastened to the appliance jacket and follows the contour of the appliance jacket Thermoelectric circuit wiring shall be exempt from this provision Note Strain relief shall be provided for all conductors leaving an enclosure For low voltage wiring strain relief...

Page 9: ... Zone Relay BoilerMate Circulator BoilerMate Thermostat 1 BoilerMate THERMOSTAT 2 3 BLACK L1 HOT L2 WHITE ON BOILER CONTROL FROM BOILER CONTROL A 24 VOLT T T T T ON BOILER CONTROL END SWITCH BoilerMate THERMOSTAT FROM BOILER CONTROL BLACK L1 HOT L2 WHITE MOTOR B 24 VOLT ZONE VALVES SCHEMATIC 3 ...

Page 10: ...dered normal and will clear as hot water is used 3 START HEATER Turn power on to the unit Dial should have the knob rotated to the 120 F mark for safety The circulator and boiler should start momentarily If not check wiring and consult the troubleshooting section in this manual 4 CHECK OPERATION The BoilerMate will begin to heat Depending upon the size of the BoilerMate output of the boiler and th...

Page 11: ...heck valve stuck open 1 Reduce temperature setpoint 2 If Boiler Return is plumbed to the suction side of a heating circulator overheating will occur when the home s heat is on Fix plumbing 3 Fully insert temperature sensor bulb 4 Repair or replace 5 Clean repair or replace Noise from BoilerMate 1 Air in boiler loop 2 Faulty circulator pump 3 Thermal expansion 4 Normal noise during initial fill 1 P...

Page 12: ...TS Number Description Part Number 1 Heat Exchanger w Gasket CH41Z 2703R003 2 Hot Water Outlet Tee 9403R123 3 Dip Tube CH 41Z only 2703R001 Dip Tube CH 80Z only 2702R001 4 Bottom Drain 9340R160 5 Dial Aquastat 2704 093 6 Safety Relief Valve 2700R116 7 Top Cap Assembly CH 41Z CH 80Z 2704R007 8 CH 41BZ Coil 2708R003 9 CH 80Z Coil 2702R002 5 7 6 2 1 3 Not shown ...

Page 13: ...and leave system connections open to prevent pressure build up Electrocution Hazard The BoilerMate must be electrically grounded Electrical supply must come from the boiler side of boiler s emergency shut off switch in order to prevent unsafe operation Chlorine Aggressive Water The water quality can significantly influence the life of this Product You should test for corrosive elements acidity tot...

Page 14: ......

Page 15: ......

Page 16: ...hode Island 02893 Part 9040 678 07 09 BoilerMate AMTROL AMTROL logo Therm X Trol Radiant EXTROL Champion and EXTROL are registered trademarks of AMTROL Inc and affiliates in the U S and elsewhere All rights reserved ...

Reviews: