7.  TROUBLESHOOTING

OVERHEATING

If  BoilerMate

®

  overheats  during  space  heating 

months, the installation may have a problem with 
the  piping  configuration.  The  water  heater  uses 
the  boiler  system  as  its  source  of  energy.  As 
such, the potential exists for the BoilerMate

®

 to be 

connected  in  a  manner  that  forces  heating  water 
through  the  exchanger  even  when  the  unit  is  off. 
This  overheating  can  present  a  scald  hazard 
and may damage the unit.
 Follow this diagram to 
determine the source of an overheating condition.

PROBLEM

POSSIBLE CAUSES

SOLUTION

No hot water

1. No power to unit

2. Air in heat exchanger loop
3. Faulty circulator or zone valve
4. Faulty BoilerMate

®

 thermostat

5. Boiler inoperable

1. Check circuit breaker, boiler emergency switch and boiler reset 

switch.

2. Purge air.  Ensure circulator is on Boiler Supply. Check air vents.
3. Check circulator and zone valve. Repair or replace if necessary.
4. Check continuity while rotating knob.  Circuit should open and close.
5. Check boiler system. Boiler must operate to generate hot water.

Insufficient hot water

1. Demand exceeds capacity
2. Temperature too low
3. Boiler lacks sufficient output

4. Fouled heat exchanger

5. Insufficient heat exchanger flow

6. Loose, missing or damaged dip tube

1. Check sizing based on household size and boiler output.
2. Increase temperature setpoint.
3. Wire for domestic hot water priority.  If problem persists add storage 

or increase tank size.

4. Check Boiler Supply/Boiler Return during cold startup.  If difference 

is less than 20F, clean heat exchanger. Install water treatment equip-
ment to prevent recurrence.  

5. Check for undersized or faulty circulator, stuck or undersized zone 

valve. Ensure all shutoff valves are open.  Check for stuck flow 
check valve. Purge boiler loop to remove air.

6. Install or replace dip tube.

Water too hot

1. Temperature set too high
2. Improper plumbing

3. Temperature sensor not fully inserted
4. Stuck zone valve
5. Flow check valve stuck open

1. Reduce temperature setpoint
2. If Boiler Return is plumbed to the suction-side of a heating circulator, 

overheating will occur when the home’s heat is on.  Fix plumbing.

3. Fully insert temperature sensor bulb. 
4. Repair or replace
5. Clean, repair or replace 

Noise from BoilerMate

®

1. Air in boiler loop
2. Faulty circulator pump
3. Thermal expansion

4. Normal noise during initial fill

1. Purge boiler loop. Check air elimination equipment.
2. Repair or replace pump.
3. Ensure the proper Therm-X-Trol

®

 or equivalent thermal expansion 

tank is installed and the air charge is adjusted properly.

4. When first pressurized, a creaking or hissing sound is normal. After 

pressurizing, the noise should stop.  Always check for leaks.

Relief valve dripping or 
opening

1. No thermal expansion tank

2. Thermal expansion tank set improperly
3. City pressure too high
4. System over temperature
5. Faulty relief valve

1. Install the proper Therm-X-Trol

®

 or equivalent thermal expansion 

tank.

2. Ensure precharge air pressure matches static water pressure.
3. Install a Pressure Reducing Valve (PRV) if city pressure is over 80psi.
4. Determine cause of over temperature condition and correct problem.
5. Replace relief valve.

Discolored water at 
faucet

1. Poor water quality

2. Sediment or suspended particles

1. Have water tested for contaminants.  Typical problems are:
    Blue/green color = copper discoloration due to low pH
    Black staining/sulfur odor = hydrogen sulfide
    White deposits = hard water
    Red staining = high iron levels
2. Install sediment filter, purge unit more often to avoid future problems.

Boiler will not operate 
when calling for hot 
water

1. Improper or loose wiring
2. Boiler high limit has been reached
3. Problem with boiler system

1. Check connections using wiring diagrams in this manual.
2. Boiler will periodically cycle on and off during operation.
3. Have boiler repaired to restore proper operation.

Circulator or zone valve 
will not operate when 
calling for hot water

1. Improper or loose wiring
2. Faulty circulator pump or zone valve

1. Check connections using wiring diagrams in this manual.
2. Repair or replace pump or zone valve.

Summary of Contents for Champion CH-41BZ

Page 1: ...URRENT EDITIONS OF THE NATIONAL PLUMBING CODE AND NATIONAL ELECTRIC CODE AS APPLICABLE THIS IS THE SAFETY ALERT SYMBOL IT IS USED TO ALERT YOU TO POTENTIAL PERSONAL INJURY AND OTHER HAZARDS OBEY ALL SAFETY MESSAGES THAT FOLLOW THIS SYMBOL TO REDUCE THE RISK OF PERSONAL INJURY AS WELL AS PROPERTY DAMAGE The heat transfer medium must be water or other nontoxic fluid having a toxicity rating or class...

Page 2: ...seepage or leakage of glycol to surfaces where humans or animals can ingest it use glycol only in double walled units so that any leaks will most likely be released to the atmosphere However a leak to a surface area may still occur so any use of glycol must be monitored closely and humans and animals should be protected from contact with the unit Do not connect the BoilerMate domestic supply with ...

Page 3: ...iler system has an EXTROL or Radiant EXTROL expansion tank and the boiler temperatures are being changed resize the EXTROL or Radiant EXTROL expansion tank 20 15 10 5 0 0 2 4 Flow GPM Pressure Drop ft 6 8 MODEL OPTION CIRCULATOR ZONE VALVE SHUTOFF VALVE VACUUM BREAKER RELIEF VALVE THERMAL EXPASION TANK DRAIN CH 41 CH 41 CH 80 Z BZ Z 4GPM If Circulator not used 3 4 Full Port or 1 STD 4 1 Included R...

Page 4: ...e T P relief valve and the tank Note Valves for reducing point of use temperature by mixing cold and hot water are available Consult a licensed plumber or the local plumbing authority BOILER PIPING 1 Plumb the circulator or zone valve onto the BOILER SUPPLY fitting 2 Pipe the BOILER RETURN connection to the boiler return fitting Be sure the return line is NOT plumbed to the suction side of any hea...

Page 5: ... 5 PIPING USING DEDICATED CIRCULATOR PUMP RECOMMENDED PIPING USING ZONE VALVE WITH EXISTING HEATING SYSTEM CIRCULATOR ...

Page 6: ...ch as one having a back flow preventer in the cold water supply line means shall be provided to control thermal expansion Contact the water supplier or local plumbing inspector on how to control this situation BOILER PIPING 1 Plumb the circulator or zone valve on the BOILER SUPPLY line If using a separate circulator the pump flange can be mounted directly to the threaded pipe marked BOILER SUPPLY ...

Page 7: ... 7 CH 41BZ PIPING USING SEPARATE CIRCULATOR PUMP RECOMMENDED PIPING USING ZONE VALVE WITH EXISTING HEATING SYSTEM CIRCULATOR ...

Page 8: ...conduit metal clad cable or raceways Power Limited Circuit Cable need not be provided with the protection specified above if it is securely fastened to the appliance jacket and follows the contour of the appliance jacket Thermoelectric circuit wiring shall be exempt from this provision Note Strain relief shall be provided for all conductors leaving an enclosure For low voltage wiring strain relief...

Page 9: ... Zone Relay BoilerMate Circulator BoilerMate Thermostat 1 BoilerMate THERMOSTAT 2 3 BLACK L1 HOT L2 WHITE ON BOILER CONTROL FROM BOILER CONTROL A 24 VOLT T T T T ON BOILER CONTROL END SWITCH BoilerMate THERMOSTAT FROM BOILER CONTROL BLACK L1 HOT L2 WHITE MOTOR B 24 VOLT ZONE VALVES SCHEMATIC 3 ...

Page 10: ...dered normal and will clear as hot water is used 3 START HEATER Turn power on to the unit Dial should have the knob rotated to the 120 F mark for safety The circulator and boiler should start momentarily If not check wiring and consult the troubleshooting section in this manual 4 CHECK OPERATION The BoilerMate will begin to heat Depending upon the size of the BoilerMate output of the boiler and th...

Page 11: ...heck valve stuck open 1 Reduce temperature setpoint 2 If Boiler Return is plumbed to the suction side of a heating circulator overheating will occur when the home s heat is on Fix plumbing 3 Fully insert temperature sensor bulb 4 Repair or replace 5 Clean repair or replace Noise from BoilerMate 1 Air in boiler loop 2 Faulty circulator pump 3 Thermal expansion 4 Normal noise during initial fill 1 P...

Page 12: ...TS Number Description Part Number 1 Heat Exchanger w Gasket CH41Z 2703R003 2 Hot Water Outlet Tee 9403R123 3 Dip Tube CH 41Z only 2703R001 Dip Tube CH 80Z only 2702R001 4 Bottom Drain 9340R160 5 Dial Aquastat 2704 093 6 Safety Relief Valve 2700R116 7 Top Cap Assembly CH 41Z CH 80Z 2704R007 8 CH 41BZ Coil 2708R003 9 CH 80Z Coil 2702R002 5 7 6 2 1 3 Not shown ...

Page 13: ...and leave system connections open to prevent pressure build up Electrocution Hazard The BoilerMate must be electrically grounded Electrical supply must come from the boiler side of boiler s emergency shut off switch in order to prevent unsafe operation Chlorine Aggressive Water The water quality can significantly influence the life of this Product You should test for corrosive elements acidity tot...

Page 14: ......

Page 15: ......

Page 16: ...hode Island 02893 Part 9040 678 07 09 BoilerMate AMTROL AMTROL logo Therm X Trol Radiant EXTROL Champion and EXTROL are registered trademarks of AMTROL Inc and affiliates in the U S and elsewhere All rights reserved ...