Register
Description
R/W
Detail
Format
41
Last linearity test checkpoint 2
result permyriad
R
Signed Int
42
Last linearity test checkpoint 3
target permyriad
R
Signed Int
43
Last linearity test checkpoint 3
result permyriad
R
Signed Int
44
Last linearity test checkpoint 4
target permyriad
R
Signed Int
45
Last linearity test checkpoint 4
result permyriad
R
Signed Int
46
Last linearity test checkpoint 5
target permyriad
R
Signed Int
47
Last linearity test checkpoint 5
result permyriad
R
Signed Int
48
Last linearity test checkpoint 6
target permyriad
R
Signed Int
49
Last linearity test checkpoint 6
result permyriad
R
Signed Int
50
Last linearity test number of test
points
R
Signed Int
51
RESERVED
52
Detector Last linearity test Date
(in Ampcontrol date format)
Time in seconds since 01-01-
2000 00:00
32 bit
Unsigned Int
53
Detector Last linearity test Date
54
Last t90 result in 0.1s (e.g 101
= 10.1s)
Unsigned Int
55
Detector last t90 test date (in
Ampcontrol date format)
Time in seconds since 01-01-
2000 00:00
32 bit
Unsigned Int
56
Detector last t90 test date (in
Ampcontrol date format)
57
Time in seconds cal cup left on
last
increments while cal cup on,
doesn't roll over past FFFF
Unsigned Int
58
Detector last Cal Cup applied
date (in Ampcontrol date
format)
Time in seconds since 01-01-
2000 00:00
32 bit
Unsigned Int
59
Detector last Cal Cup applied
date (in Ampcontrol date
format)
60
Time in seconds last spent in
telemetry test
increments during active test
Unsigned Int
61
Detector last telemetry test date
(in Ampcontrol date format)
Time in seconds since 01-01-
2000 00:00
32 bit
Unsigned Int
62
Detector last telemetry test date
(in Ampcontrol date format)
63
Detector Last in-situ adjustment
date (Ampcontrol date format)
Time in seconds since 01-01-
2000 00:00
32 bit
Unsigned Int
64
Detector Last in-situ adjustment
date (Ampcontrol date format)
65
Detector coms error count
clear on sensor power up,
accumulate and hold at FFFF
Signed Int
66
Detector hours of run time since
build/overhaul
max out at FFFF, don't roll
over
Unsigned Int