REMOTE OPERATION
The GG2 Display supports two-way communication over a Modbus or iMAC system.
7.1 GG2 Detector Type Table
Table 16: GG2 Detector Type Table
Gas
Type
Detector
Technology
Measurement Range
Ampcontrol Part
Numbers
CH4
Catalytic
0-5% v/v
177871
CH4
IR
0-5% v/v
177870
CO2
IR
0-2% v/v
180734
CO2
IR
0-5% v/v
180733
CO
Electrochemical
0-50ppm
177873
CO
Electrochemical
0-100ppm
177874
O2
Electrochemical
0-25% v/v
177872
7.2 Modbus
Register Map
All values can be assumed to be the Modbus default endianness, big-endian. Any exceptions to this will
be noted in the Format column.
7.2.1.1 Safety Registers
Register
Description
R/W
Detail
Format
1
Detector gas reading permyriad
- unaffected by telemetry test
R
Permyriad of full scale, see
Gas Reading Units6.4.1
Signed Int
2
Bit-inverted Detector gas
reading permyriad - unaffected
by telemetry test
R
Permyriad of full scale, See
Gas Reading Units6.4.1
Signed Int, bit
inversion
3
Heartbeat
R
Increments on each cycle,
nominally every 100ms.
Unsigned Int
4
RESERVED
7.2.1.2 Operational Registers
Register
Description
R/W
Detail
Format
5
Detector gas reading permyriad
- may be forced by telemetry
test.
R
Permyriad of full scale, see
Gas Reading Units6.4.1
Signed Int
6
– bit 0
SP1 flag
R
1 = flag set
bit
6
– bit 1
SP2 flag
R
1 = flag set
bit
6
– bit 2
SP3 flag
R
1 = flag set
bit
6
– bit 3
Cal cup on
R
1 = cup on
bit
6
– bit 4
Calibration due (every 6
months)
R
1 = calibration due
bit
6
– bit 5
T90 test due (every 31 days)
R
1 = T90 test due
bit
6
– bit 6
Detector present
R
1 = detector present
bit
6
– bit 7
4-20mA loop activation
R
1 = 4-20mA loop active
bit