2-5
84-55
TROUBLESHOOTING
9.2.6 MMI fails to power
on
PLC not powered
PLC ok but MMI to PLC
connections
MMI cable connection ok
but still not powered on
Check fuse F4 if blown
then change & check
power on indication on
PLC if not rectify by the
help of help of wiring
diagram, if wiring ok then
PLC faulty contact AMF
Reece for new & replace
Check MMI cable
connection
Chance of MMI faulty or
PLC to MMI connection
Port is faulty contact AMF
Reece for new & replace
9.2.7 DC motor for jig
movement fails to
functional
DC motor card in cabinet
is not powered
Necessary command
signals for function is
missing
DC card faulty
Check Fuse F5 if Blown
then Change if still not
functional then check 24
V DC power at input
terminals, rectify by the
help of wiring diagram
Go to MMI System Check
Menu – Output test- DC
drive speed 1 screen &
give command for test.
While test command is
on check 24 V DC
between P24 sleeve wire
terminal & Y31,Y33
sleeve wire terminals. If
no voltage rectify by
wiring diagram, if signal
is ok then check DC
voltage at M+ & M-
sleeve terminals turn the
speed potentiometer on
card to anticlockwise DC
voltage at M+ & M-
should increase. if it
increases check the DC
motor power cable &
rectify by wiring diagram.