          UPS + Isolation                        User Manual 

   

© 2020 AMETEK Electronic Systems Protection | Technical Support: 1-800-645-9721 | surgex.com

                                                                                                            

   

                    

 

                               

   

                    

 

 

 

 

Model #: ABCE1442-11R / Part #:UPS-1440-Li-ISO 

Rack Mount UPS Specifications

 

 

Front Panel Controls

 

  Power On/Off

 

  Test

 

  Load Level LED Gauge

 

  Battery Charge LED Gauge

 

  Voltage Manager Boost LED

 

  Voltage Output  On LED

 

  Voltage Manager Buck LED

 

  On Battery LED

 

  Replace Battery LED

 

  Overload LED

 

  Fault Code LED

 

  System  Over Temperature LED

 

 

Rear Panel Information and Controls

 

  Integrated Switched Power Distribution Unit

 

(Requires SNMP / Web Card)

 

  Configuration Manager  DIP Switches

 

  Communications Manager DB9 Port, USB Port

 

  Circuit Breaker (AC and DC)

 

  AC Inlet Module

 

  Communication Option Slot: SNMP / Web Card, Isolated

 

Relay Contacts  Card, or Remote Off Card

 

  DC External Battery Cabinet Connector

 

  Fan (Forced Cooling)

 

 

Internal Batteries

 

  User Hot-Swappable (See Instruction Manual)

 

  Type: 12 Volt, High Rate 23W

 

  Quantity: 4 Batteries

 

  Recharge Time: 6 Hours to 80%, 24 Hours to Full Charge

 

(For Internal Batteries Only)

 

Environmental

 

  Temperature:  0 - +40

(32 to 104

) Operating

 

-20 to 60

(-40 to 140

) Shipment/

 

Storage

 

  Humidity: 

5 to 90% Non-Condensing (Operating, 
Shipment/Storage)

 

  Altitude: 

3,000m (10,000 ft) max. Operating;

 

12,000m (40,000 ft) max. Shipment/Storage

 

 

Safety Agency and EMC Compliance:

 

All Units are Listed by UL and Marked With the UL/cUL Marking

 

 

Standard UPS: 
Products Listed to:

 

  UL1778 5th Edition

 

  CSA 22.2 Nos. 107.3-14

 

 

Products in Compliance with:

 

  FCC-Part 15, Subpart B, Sections 15.107b & 15.109b

 

Class A Digital Device*

 

  CISPR11:2009, A1; 2010, Class A*

 

  IEC61000-4-2, Electrostatic Discharge

 

  IEC61000-4-3, Radiated Electromagnetic Field Immunity

 

  IEC61000-4-4,  Electrical  Fast Transient/Burst Immunity

 

  IEC61000-4-5, Surge Immunity

 

  IEC61000-4-6, Immunity to Conducted Radio Frequency

 

Disturbances

 

  IEC61000-4-8, Power Frequency Magnetic Field Immunity

 

  IEC61000-4-11,  Voltage Dips, Short Interruptions and

 

Voltage Variations

 

 

*Note:  Class B is Available as an Option

 

Please Consult Your SurgeX Sales Representative

 

 

RoHS Compliance:

 

All Products (Standard and Medical) are RoHS Compliant

 

1440 VA MODELS  TYPICAL RUN-TIMES (MINs)

 

 

10% (130W)

 

20% (259W)

 

30% (389W)

 

40% (518W)

 

50% (648W)

 

60% (778W)

 

70% (907W)

 

80% (1036W)

 

90% (1166W)

 

100% (1296W)

 

Internal Batteries Only

 

90

 

38

 

20

 

12

 

9

 

6

 

5

 

4

 

2.8

 

2.5

 

In 1) E4804-12

 

480

 

183

 

110

 

72

 

59

 

51

 

35

 

30

 

25.8

 

24.5

 

In 2) E4804-12

 

870

 

328

 

200

 

132

 

109

 

96

 

65

 

56

 

48.8

 

46.5

 

In 3) E4804-12

 

1260

 

473

 

290

 

192

 

159

 

141

 

95

 

82

 

71.8

 

68.5

 

In 4) E4804-12

 

1650

 

618

 

380

 

252

 

209

 

186

 

125

 

108

 

94.8

 

90.5

 

In 5) E4804-12

 

2040

 

763

 

470

 

312

 

259

 

231

 

155

 

134

 

117.8

 

112.5

 

In 6) E4804-12

 

2430

 

908

 

560

 

372

 

309

 

276

 

185

 

160

 

140.8

 

134.5

 

In 7) E4804-12

 

2820

 

1053

 

650

 

432

 

359

 

321

 

215

 

186

 

163.8

 

156.5

 

In 8) E4804-12

 

3210

 

1198

 

740

 

492

 

409

 

366

 

245

 

212

 

186.8

 

178.5

 

 

NOISE  REJECTION-ISOLATION: 

With unit under power  and an ANSI/IEEE  C62.41Cat.  A pulse applied  either normal  or common  mode at the input,  the noise output voltage will be less than 

10V normal mode and less than 0.5V common mode in all four quadrants (CM-NM, NM-NM, CM-CM, NM-CM).

 

 

SURGE  VOLTAGE  WITHSTAND  CAPABILITY: 

Tested  under  power  to ANSI/IEEE  C62.41  Cat. A & B (formerly  IEEE587-1980).  Cat. A - 6000V @ 200 amps, 0.5 usec risetime, 100 kHZ decay, 

Cat. B - 6000V @ 500 amps, 0.5 usec risetime, 100 kHZ decay.

 

Warranty/Support:  

SurgeX  warrants the electronics and transformers used in its uninterruptible power  managers to be free from defects in materials and workmanship  for a period  of five years 

from the date of shipment.  Batteries  are warranted  for a period  of two years from the date of shipment. For service or support on any SurgeX product, please contact  SurgeX  Technical 
Support at (800) 645-9721 or visit the SurgeX website at 

www.surgex.com

.

 

 

Battery Life Disclaimer: 

SurgeX

s standard battery warranty applies  only to UPS and UPS products  which are continuously connected to AC mains  power, except during utility power 

outages. Products which are regularly and intentionally disconnected from AC mains power will experience battery discharge/charge cycles potentially far more numerous than those for which the 
battery was designed. As a result, products used in such applications  will experience substantially reduced battery life. For that reason, SurgeX

s standard battery warranty does not apply 

for applications  in which the UPS or UPS product is regularly and intentionally disconnected from AC mains power. SurgeX UPS and UPS products used in such applications shall receive a 90 
day warranty on batteries.

 

Summary of Contents for SurgeX UPS-1440-Li-ISO

Page 1: ...UPS Isolation Transformer Battery Backup UPS 1440 Li ISO UPS 2200 Li ISO UPS 3000 Li ISO 2020 AMETEK Electronic Systems Protection 1 800 645 9721 surgex com A01 00147 Rev A...

Page 2: ...TABLE OF CONTENTS 1 0 Safety Instructions 3 2 0 Installation 7 3 0 Operation 12 4 0 Maintenance 17 5 0 Troubleshooting 22 6 0 Specifications 23...

Page 3: ...also occur Attention The attention warning symbol is used to indicate situations and conditions that can cause operator injury and or equipment damage Other warning symbols may appear along with the D...

Page 4: ...UPS Isolation Transformer User Manual 2020 AMETEK Electronic Systems Protection Technical Support 1 800 645 9721 surgex com 2 Alternating Current Refer to instruction manual booklet Two person lift...

Page 5: ...teries used by SurgeX The batteries used in this UPS are sealed lead acid and are maintenance free Proper disposal of batteries is required Refer to your local codes for disposal of batteries UPS Rati...

Page 6: ...The UPS is CLASS 1 equipment Do not attempt to power the UPS from any receptacle except a properly grounded receptacle that matches the input plug provided with the UPS Do not place the UPS near wate...

Page 7: ...ck connectors when maintenance or service work inside the UPS is necessary The battery should be disconnected from the UPS by unplugging at its quick connectors when maintenance or service work inside...

Page 8: ...used in accordance with the instructions may cause harmful interference to radio communications However there is no guarantee that interference will not occur in a particular installation If this equi...

Page 9: ...tart Guide This unit is shipped with the internal batteries disconnected Before starting the UPS please follow these battery connection instructions 1 Remove UPS from the box Some units may require 2...

Page 10: ...UPS Isolation Transformer User Manual 2020 AMETEK Electronic Systems Protection Technical Support 1 800 645 9721 surgex com 8...

Page 11: ...nit 2 Carefully lift the unit out of the outer carton 3 Store the carton for future use Place the unit in a protectedarea that has adequate airflow and is free of humidity flammable gas and corrosion...

Page 12: ...inets attach 1 angled mounting bracket to each side of the UPM and or each side of the battery cabinet using the 8 screws provided 6 For 4U UPMs attach 2 angled mounting brackets to each side of the U...

Page 13: ...erials for the carrier or place of purchase and file a claim for shipping damage 1 File with the carrier within 15 days of receipt of the equipment 2 Send a copy of the damage claim within 15 days to...

Page 14: ...will cold start the UPS on its internal battery with no incoming AC present When the UPS is on pressing the On Off button for more than 2 seconds will turn off the UPS output power Test Silence Butto...

Page 15: ...ly The SF symbol will be displayed on the front panel of the UPS if it is connected to an improperly wiredAC receptacle This is to indicate a missing safety ground wire or a reversal in phase and neut...

Page 16: ...roperly connected and initially checked turn on the UPS by pressing and holding the front panel On Off switch for 3 seconds Operational Tests Observe the front panel of the UPS The following table sho...

Page 17: ...powered off perform an initial test of the UPS backup function by pressing the Test Silence button on the front panel During this test the Battery LED on the front panel should briefly illuminate It...

Page 18: ...utilizing MopUPS Pro software you can configure the system to automatically self test periodically The UPS is shipped with a charged battery but some discharge naturally occurs during storage and ship...

Page 19: ...te which makes it possible to use them in any physical orientation The batteries are designed to last from two to five years Their actual life span will depend on several factors including how often p...

Page 20: ...r serviceable non medical units only The battery compartment is accessed by removing the front panel as described in the following instructions No other user serviceable parts are contained in this UP...

Page 21: ...m The UPS allows the battery to be hot swapped while the system is running NOTE Changing the batteries in this UPS is designed to be a safe and simple procedure Batteries may be replaced while the UPS...

Page 22: ...a risk of electrical shock and high short circuit current The following precautions should be observed when working with batteries Remove watches rings or other metal objects Use tools with insulated...

Page 23: ...20 AMETEK Electronic Systems Protection Technical Support 1 800 645 9721 surgex com UPS Battery Replacement Instructions 1440 VA See Instructions for Returning a Depleted Battery Pack for instructions...

Page 24: ...er cord is not plugged in 4 Rear panel circuit breaker is tripped 1 Press and hold the On Off switch for 3 seconds min 2 Check wall socket and test for proper line voltage 3 Plug in input power cord 4...

Page 25: ...tive Load 4 On Battery Online Efficiency w o Charger 92 Input Voltage 120 Input Current 12 0 Amps Input Voltage Range w o Using Battery 96 to 144 Volts Output Voltage 120 Output Current VA Watts 12 0...

Page 26: ...518W 50 648W 60 778W 70 907W 80 1036W 90 1166W 100 1296W Internal Batteries Only 90 38 20 12 9 6 5 4 2 8 2 5 Internal 1 E4804 12 480 183 110 72 59 51 35 30 25 8 24 5 Internal 2 E4804 12 870 328 200 1...

Page 27: ...ve Load 4 On Battery Online Efficiency w o Charger 95 Input Voltage 120 Input Current 24 0 Amps Output Voltage 120 Output Current VA Watts 18 5 16 5 Amps Input Voltage Range w o Using Battery 96 to 14...

Page 28: ...1 E4804 12 281 135 85 59 42 32 5 23 19 14 5 12 Internal 2 E4804 12 467 225 140 99 70 54 5 38 31 5 23 5 19 5 Internal 3 E4804 12 653 315 195 139 98 76 5 53 44 32 5 27 Internal 4 E4804 12 839 405 250 17...

Page 29: ...attery Online Efficiency w o Charger 95 Input Voltage 208 Input Current 16 0 Amps Output Voltage 230 and 115 Output Current VA Watts 12 0 11 5 and 24 0 21 6 Amps Input Voltage Range w o Using Battery...

Page 30: ...58 20 14 10 7 6 4 8 3 2 3 Internal 1 E4804 12 239 178 62 42 30 24 16 10 8 9 2 7 5 Internal 2 E4804 12 389 298 104 70 50 41 26 16 8 15 2 12 Internal 3 E4804 12 539 418 146 98 70 58 36 22 8 21 2 16 5 In...

Reviews: