UPS + Isolation Transformer User Manual
© 2020 AMETEK Electronic Systems Protection | Technical Support: 1-800-645-9721 | surgex.com
16
Reference the below UPS fault code chart to identify the status of the UPS.
UPS Status Code
Definition
IF
Inverter fault
BE
Back-Feed fault
HL
Unit is off due to a high line
LL
Unit is off due to a low line
DB
Unit is off due to a low battery
FF
Fan fault
SF
Site wiring fault
NOTE:
•
If the UPS is on continuously, it will perform an auto battery test every six days.
•
If you are utilizing MopUPS Pro software, you can configure the system to
automatically self-test periodically.
•
The UPS is shipped with a charged battery, but some discharge naturally occurs
during storage and shipment. You may use the UPS immediately, but you should
realize that backup time may be less than the stated rating until the UPS battery has
had at least six hours to charge.
•
SurgeX recommends that you do not plug laser printers into the UPS. Laser printers
are known to draw large amounts of current when the fuser/heater assembly is
energized. Laser printers can easily overload the UPS or create a low voltage
condition that can interfere with the operation of the Voltage Manager circuit.