          UPS + Isolation                        User Manual 

   

© 2020 AMETEK Electronic Systems Protection | Technical Support: 1-800-645-9721 | surgex.com

                                                                                                            

   

                    

 

                               

   

                    

 

 

 

Model #: ABCE3002-21R / Part #: UPS-3000-Li-ISO 

Rack Mount UPS Specifications 

 

Front  Panel  Controls  

Environmental

 

    

Power On/Off 

    

Temperature: 0 - +40

C (32 to 104

0

F) Operating 

    

Test  

-20 to 60

C (-40 to 140

F) Shipment/ 

    

Load  Level  LED  Gauge  

Storage 

    

Battery  Charge  LED  Gauge  

    

Humidity:  

5 to 90%  Non-Condensing  (Operating, 

Shipment/Storage) 

    

Voltage Manager Boost LED 

    

Altitude: 

3,000m (10,000 ft) max. Operating; 

    

Voltage Output On LED 

12,000m (40,000 ft) max. Shipment/Storage. 

    

Voltage  Manager  Buck  LED 

    

On  Battery  LED  

Safety  Agency  and  EMC  Compliance:

 

    

Replace  Battery  LED  

All  Units  are  Listed  by  UL  and  Marked  with  the  UL/cUL  Marking. 

    

Overload LED 

Standard UPM:

 

    

Fault  Code  LED  

Products Listed To:

 

    

System  Over  Temperature LED  

  

UL  IEC62040, CE  Mark  with  CB  Report 

 

Rear  Panel  Information and  Controls  

Products  in compliance with:

 

    

1.8 Meter Power Cord with C20 to L6-20 Plug 

    

FCC-Part 15, Subpart B, Sections 15.107b & 15.109b 

    

Eight (8) NEMA 5-20R and (1) NEMA L6-20 Receptacles 

Class  A Digital  Device* 

    

Configuration Manager DIP Switches 

    

CISPR11:2009, A1; 2010, Class A* 

    

Communications Manager  DB9  Port,  USB  Port  

    

IEC61000-4-2, Electrostatic Discharge 

    

Circuit  Breaker  

    

IEC61000-4-3, Radiated  Electromagnetic Field  Immunity 

    

AC Inlet Module 

    

IEC61000-4-4, Electrical Fast Transient/Burst Immunity 

    

SNMP  Slot  (Contact  Factory)  

    

IEC61000-4-5, Surge Immunity 

    

IEC61000-4-6, Immunity to Conducted Radio Frequency 

Internal  Batteries 

Disturbances 

    

User  Hot-Swappable (See  Instruction Manual)  

    

IEC61000-4-8, Power  Frequency Magnetic  Field  Immunity 

    

Type: 12 Volt, High Rate 23W 

    

IEC61000-4-11, Voltage Dips, Short Interruptions, and 

    

Quantity: 8 Batteries 

Voltage Variations 

    

Recharge Time:  8 Hours  to  80%,  24  Hours  to Full  Charge  

*Note: Class B is Available as an Option

 

Please  Consult  Your  SurgeX Sales  Representative

 

3000VA   TYPICAL  RUN-TIMES (MINs)

 

 

 

10% (248W) 

 

20% (297W) 

 

30% (745W) 

 

40% (993W) 

 

50% (1242W) 

 

60% (1490W) 

 

70% (1739W) 

 

80% (1987W) 

 

90% (2235W) 

 

100%  (2484W) 

Internal  Batteries  Only 

89 

58 

20 

14 

10 

4.8 

3.2 

Internal  + 1) E4804-12 

239 

178 

62 

42 

30 

24 

16 

10.8 

9.2 

7.5 

Internal  + 2) E4804-12 

389 

298 

104 

70 

50 

41 

26 

16.8 

15.2 

12 

Internal  + 3) E4804-12 

539 

418 

146 

98 

70 

58 

36 

22.8 

21.2 

16.5 

Internal  + 4) E4804-12 

689 

538 

188 

126 

90 

75 

46 

28.8 

27.2 

21 

Internal  + 5) E4804-12 

839 

658 

230 

154 

110 

92 

56 

34.8 

33.2 

25.5 

Internal  + 6) E4804-12 

989 

778 

272 

182 

130 

109 

66 

40.8 

39.2 

30 

Internal  + 7) E4804-12 

1139 

898 

314 

210 

150 

126 

76 

46.8 

45.2 

34.5 

Internal  + 8) E4804-12 

1289 

1018 

356 

238 

170 

143 

86 

52.8 

51.2 

39 

NOISE  REJECTION-ISOLATION:  

With  unit  under  power and  an  ANSI/IEEE C62.41Cat. A pulse  applied  either  normal  or  common  mode  

at the input,  the noise  output  voltage  will be less  than  10V  normal  mode  and  less  than  0.5V common  mode  in all four  quadrants  (CM-NM,  NM- 
NM,  CM-CM,  NM-COM). 

 

SURGE  VOLTAGE WITHSTAND CAP ABILITY: 

Tested  under  power  to  ANSI/IEEE C62.41  Cat.  A &  B (formerly IEEE587-1980). Cat.  A - 

6000V  @ 200 amps,  0.5 usec  risetime,  100  kHZ decay,  Cat.  B - 6000V  @ 500  amps,  0.5 usec  risetime,  100  kHZ  decay. 

 

Warranty/Support:  

SurgeX warrants the elec tronics and  transformers used  in its  uninterruptib le power managers  to be free  from defects 

in materials  and  workmanship for  a period  of five years  from  the date of shipment.   Batteries  are warranted  for a period  of two years  from the date 
of shipment.  For service  or support  on any  SurgeX product,  please  contact  SurgeX Technical  Support  at (800)  645-9721  or visit  the SurgeX 
website  at 

ww.surgex.com

 

Battery  Life  Disclaimer

: SurgeX

’s standard  battery  warranty  applies  only  to UPS  and UPM  products  which  are continuously connected  to AC 

mains  power,  except   during  utility  power  outages.  Products  which  are regularly  and  intentionally disconnected from  AC mains  power  will 
experience battery  discharge/charge cycles  potentially  far more  numerous  than  those  for which  the battery  was designed.  As a result,  products 
used  in such  applications will experience substantially reduced  battery  life. For that  reason,  SurgeX

’s standard  battery  warranty  does  not apply 

for applications in which  the UPS  or UPM  product  is regularly  and  intentionally disconnected from  AC mains  power.  SurgeX UPS  products  used 
in such  applications shall  receive  a 90 day warranty  on batteries. 

 

Summary of Contents for SurgeX UPS-1440-Li-ISO

Page 1: ...UPS Isolation Transformer Battery Backup UPS 1440 Li ISO UPS 2200 Li ISO UPS 3000 Li ISO 2020 AMETEK Electronic Systems Protection 1 800 645 9721 surgex com A01 00147 Rev A...

Page 2: ...TABLE OF CONTENTS 1 0 Safety Instructions 3 2 0 Installation 7 3 0 Operation 12 4 0 Maintenance 17 5 0 Troubleshooting 22 6 0 Specifications 23...

Page 3: ...also occur Attention The attention warning symbol is used to indicate situations and conditions that can cause operator injury and or equipment damage Other warning symbols may appear along with the D...

Page 4: ...UPS Isolation Transformer User Manual 2020 AMETEK Electronic Systems Protection Technical Support 1 800 645 9721 surgex com 2 Alternating Current Refer to instruction manual booklet Two person lift...

Page 5: ...teries used by SurgeX The batteries used in this UPS are sealed lead acid and are maintenance free Proper disposal of batteries is required Refer to your local codes for disposal of batteries UPS Rati...

Page 6: ...The UPS is CLASS 1 equipment Do not attempt to power the UPS from any receptacle except a properly grounded receptacle that matches the input plug provided with the UPS Do not place the UPS near wate...

Page 7: ...ck connectors when maintenance or service work inside the UPS is necessary The battery should be disconnected from the UPS by unplugging at its quick connectors when maintenance or service work inside...

Page 8: ...used in accordance with the instructions may cause harmful interference to radio communications However there is no guarantee that interference will not occur in a particular installation If this equi...

Page 9: ...tart Guide This unit is shipped with the internal batteries disconnected Before starting the UPS please follow these battery connection instructions 1 Remove UPS from the box Some units may require 2...

Page 10: ...UPS Isolation Transformer User Manual 2020 AMETEK Electronic Systems Protection Technical Support 1 800 645 9721 surgex com 8...

Page 11: ...nit 2 Carefully lift the unit out of the outer carton 3 Store the carton for future use Place the unit in a protectedarea that has adequate airflow and is free of humidity flammable gas and corrosion...

Page 12: ...inets attach 1 angled mounting bracket to each side of the UPM and or each side of the battery cabinet using the 8 screws provided 6 For 4U UPMs attach 2 angled mounting brackets to each side of the U...

Page 13: ...erials for the carrier or place of purchase and file a claim for shipping damage 1 File with the carrier within 15 days of receipt of the equipment 2 Send a copy of the damage claim within 15 days to...

Page 14: ...will cold start the UPS on its internal battery with no incoming AC present When the UPS is on pressing the On Off button for more than 2 seconds will turn off the UPS output power Test Silence Butto...

Page 15: ...ly The SF symbol will be displayed on the front panel of the UPS if it is connected to an improperly wiredAC receptacle This is to indicate a missing safety ground wire or a reversal in phase and neut...

Page 16: ...roperly connected and initially checked turn on the UPS by pressing and holding the front panel On Off switch for 3 seconds Operational Tests Observe the front panel of the UPS The following table sho...

Page 17: ...powered off perform an initial test of the UPS backup function by pressing the Test Silence button on the front panel During this test the Battery LED on the front panel should briefly illuminate It...

Page 18: ...utilizing MopUPS Pro software you can configure the system to automatically self test periodically The UPS is shipped with a charged battery but some discharge naturally occurs during storage and ship...

Page 19: ...te which makes it possible to use them in any physical orientation The batteries are designed to last from two to five years Their actual life span will depend on several factors including how often p...

Page 20: ...r serviceable non medical units only The battery compartment is accessed by removing the front panel as described in the following instructions No other user serviceable parts are contained in this UP...

Page 21: ...m The UPS allows the battery to be hot swapped while the system is running NOTE Changing the batteries in this UPS is designed to be a safe and simple procedure Batteries may be replaced while the UPS...

Page 22: ...a risk of electrical shock and high short circuit current The following precautions should be observed when working with batteries Remove watches rings or other metal objects Use tools with insulated...

Page 23: ...20 AMETEK Electronic Systems Protection Technical Support 1 800 645 9721 surgex com UPS Battery Replacement Instructions 1440 VA See Instructions for Returning a Depleted Battery Pack for instructions...

Page 24: ...er cord is not plugged in 4 Rear panel circuit breaker is tripped 1 Press and hold the On Off switch for 3 seconds min 2 Check wall socket and test for proper line voltage 3 Plug in input power cord 4...

Page 25: ...tive Load 4 On Battery Online Efficiency w o Charger 92 Input Voltage 120 Input Current 12 0 Amps Input Voltage Range w o Using Battery 96 to 144 Volts Output Voltage 120 Output Current VA Watts 12 0...

Page 26: ...518W 50 648W 60 778W 70 907W 80 1036W 90 1166W 100 1296W Internal Batteries Only 90 38 20 12 9 6 5 4 2 8 2 5 Internal 1 E4804 12 480 183 110 72 59 51 35 30 25 8 24 5 Internal 2 E4804 12 870 328 200 1...

Page 27: ...ve Load 4 On Battery Online Efficiency w o Charger 95 Input Voltage 120 Input Current 24 0 Amps Output Voltage 120 Output Current VA Watts 18 5 16 5 Amps Input Voltage Range w o Using Battery 96 to 14...

Page 28: ...1 E4804 12 281 135 85 59 42 32 5 23 19 14 5 12 Internal 2 E4804 12 467 225 140 99 70 54 5 38 31 5 23 5 19 5 Internal 3 E4804 12 653 315 195 139 98 76 5 53 44 32 5 27 Internal 4 E4804 12 839 405 250 17...

Page 29: ...attery Online Efficiency w o Charger 95 Input Voltage 208 Input Current 16 0 Amps Output Voltage 230 and 115 Output Current VA Watts 12 0 11 5 and 24 0 21 6 Amps Input Voltage Range w o Using Battery...

Page 30: ...58 20 14 10 7 6 4 8 3 2 3 Internal 1 E4804 12 239 178 62 42 30 24 16 10 8 9 2 7 5 Internal 2 E4804 12 389 298 104 70 50 41 26 16 8 15 2 12 Internal 3 E4804 12 539 418 146 98 70 58 36 22 8 21 2 16 5 In...

Reviews: