Rack Mount UPS Specifications
Front Panel Controls
-20 to 60
0
C (-40 to 140
0
F) Shipment/
Power On/Off
Storage
Test
Humidity:
5 to 90% Non-Condensing (Operating,
Load Level LED Gauge
Shipment/Storage)
Battery Charge LED Gauge
Altitude:
3,000m (10,000 ft) max. Operating;
12,000m (40,000 ft) max. Shipment/Storage.
Voltage Manager Boost LED
Voltage Output On LED
Safety Agency and EMC Compliance:
Voltage Manager Buck LED
All Units are Listed by UL and Marked with the UL/cUL Marking.
On Battery LED
Standard UPS:
Replace Battery LED
Products Listed To:
Overload LED
UL1778 5th Edition
Fault Code LED
CSA 22.2 Nos. 107.3-14
System Over Temperature LED
Products in compliance with:
Rear Panel Information and Controls
FCC-Part 15, Subpart B, Sections 15.107b & 15.109b
6 Foot Power Cord with NEMA L5-30P Plug
Class A Digital Device*
Configuration Manager DIP Switches
CISPR11:2009, A1; 2010, Class A*
Communications Manager DB9 Port, USB Port
IEC61000-4-2, Electrostatic Discharge
Circuit Breaker
IEC61000-4-3, Radiated Electromagnetic Field Immunity
AC Inlet Module
IEC61000-4-4, Electrical Fast Transient/Burst Immunity
SNMP Slot (Contact Factory)
IEC61000-4-5, Surge Immunity
IEC61000-4-6, Immunity to Conducted Radio Frequency
Internal Batteries
Disturbances
User Hot-Swappable (See Instruction Manual)
IEC61000-4-8, Power Frequency Magnetic Field Immunity
Type: 12 Volt, High Rate 23W
IEC61000-4-11, Voltage Dips, Short Interruptions, and
Quantity: 8 Batteries
Voltage Variations
Recharge Time: 8 Hours to 80%, 24 Hours to Full Charge
*
Note: Class B is Available as an Option
Environmental
Please Consult Your SurgeX Sales Representative
Temperature: 0 - +40
0
C (32 to 104
0
F) Operating
2200VA TYPICAL RUN-TIMES (MINs)
10% (198W)
20%
(396W)
30% (594W)
40%
(792W)
50% (990W)
60%
(1188W)
70%
(1386W)
80%
(1584W)
90% (1782W)
100%
(1980W)
Internal Batteries Only
95
45
30
19
14
10.5
8
6.5
5.5
4.5
Internal + 1) E4804-12
281
135
85
59
42
32.5
23
19
14.5
12
Internal + 2) E4804-12
467
225
140
99
70
54.5
38
31.5
23.5
19.5
Internal + 3) E4804-12
653
315
195
139
98
76.5
53
44
32.5
27
Internal + 4) E4804-12
839
405
250
179
126
98.5
68
56.5
41.5
34.5
Internal + 5) E4804-12
1025
495
305
219
154
120.5
83
69
50.5
42
Internal + 6) E4804-12
1211
585
360
259
182
142.5
98
81.5
59.5
49.5
Internal + 7) E4804-12
1397
675
415
299
210
164.5
113
94
68.5
57
Internal + 8) E4804-12
1583
765
470
339
238
186.5
128
106.5
77.5
64.5
NOISE REJECTION-ISOLATION:
With unit under power and an ANSI/IEEE C62.41Cat. A pulse applied either normal or common mode at the input, the noise output
voltage will be less than 10V normal mode and less than 0.5V common mode in all four quadrants (CM-NM, NM- NM, CM-CM, NM-COM).
SURGE VOLTAGE WITHSTAND CAPABILITY:
Tested under power to ANSI/IEEE C62.41 Cat. A & B (formerly IEEE587 -1980). Cat. A -
6000V @ 200 amps, 0.5 usec risetime, 100 kHZ decay, Cat. B - 6000V @ 500 amps, 0.5 usec risetime, 100 kHZ decay.
Warranty/Support:
SURGEX w warrants the electronics and transformers used in its unin terrup tible power managers to be free fro m defects in materials and
workmanship for a period of five years from the date of shipment. Batteries are warranted for a period of two years from the date of shipment. For service or support on any
SURGEX product, please contact SURGEX Technical Support at (800) 645-9721 or visit the SURGEX website at
www.surgex.com
.
Battery Life Disclaimer
:
SURGEX’s
standard battery warranty applies only to UPS and UPS products which are continuously connected to AC mains power, except during
utility power outages. Products which are regularly and intentionally disconnected from AC mains power will experience battery discharge/charge cycles potentially far more
numerous than those for which the battery was designed. As a result, products used in such applications will experience substantially reduced battery life. For that reason,
SURGEX’s
standard battery warranty does not apply for applications in which the UPS or UPS product is regularly and intentionally disconnected from AC mains power.
SURGEX UPS and UPS products used in such applications shall receive a 90 day warranty on batteries.