March 1, 2001 7-2
193111-047
Programming Your SCR2000 Control
23. AUTO EQ. DAY The day of the week that an
equalize charge cycle is
performed when the auto
equalize function is “ON” and
the auto equalize type is set to
“DAY”.
1 = Sun.
2 = Mon.
3 = Tue.
4 = Wed.
5 = Thu.
6 = Fri.
7 = Sat., factory setting
Key in data and press enter.
24. AUTO EQ. Sets the auto equalize function
on or off.
0 = Auto equalize “OFF”
1 = Auto equalize “ON”
factory setting
Key in data and press enter.
25. T.O.D. START Sets the time of day start time
(0000 to 2359, 24 hour format).
See START MODE.
Key in data and press enter.
26. DELAYED START Sets the delayed start time
interval (01H 00m to
23H 59M).
Factory = 01H 00M
See START MODE.
Key in data and press enter.
27. BLOCK START Sets the beginning time of the
time of day blockout function
(0000 to 2359, 24 hour format).
See START MODE.
Key in data and press enter.
28. BLOCK END Sets the ending time of the
time of day blockout function
(0000 to 2359, 24 hour format).
See START MODE.
Key in data and press enter.
29. START Sets the start override function
OVERRIDE that allows the operator to
override any of the charger
start modes ( i.e.; delayed
start, time of day start, or time
of day blockout).
0 = Off
1 = On, factory setting
Key in data and press enter.
30. START MODE Selects the desired start mode
for the start of the charge
cycle.
0 = Automatic mode
“AUTO”, factory setting
1 = Time of day start mode
“T.O.D.S.”
2 = Delay start mode
“DLY.ST.”
3 = Time of day blockout
“T.O.D.B.”
Key in data and press enter.
31. FORMING Sets the number of forming
CYCLES cycles for a new battery by
disabling the low current shut-
down and setting VT Termina-
tion mode for the programmed
number of cycles (00 to 30).
00 = factory setting
Key in data and press enter.
WARNING: Enabling the Finish
Cell Forming feature will cause the
charger to continue to run for a period
of time if the battery has been
disconnected before Charge Complete
or pressing the Manual Stop key. This
condition will continue until the
programmed number of cycles have
been completed. The battery should
never be disconnected while a charge
is in progress.