Programming Your SCR2000 Control
32. SPECIAL Special option modes see below:
OPTION
0 = OFF
1 = “P.T.S.“ Push to start mode.
The charger will not start until
the “ENTER” key is pressed.
2 = “F.L.O.” Fault lockout
The charger will not restart until
any faults are reset by pressing
the “ENTER” key with no battery
connected.
Key in data and press enter.
33. CYCLE AH The ampere-hour setting of the
SIZE charger during the charge cycle.
This value cannot exceed the
maximum charger output rating.
(NOT PROGRAMMABLE)
34.
LOW BATTERY
Sets the point in V/C at which a
REJECT
battery will be rejected if it is
lower. Only enter the data to the
right of the decimal point.
(1.75 to 1.99)
Factory = 1.75
Key in data and press enter.
35.
HIGH BATTERY
Sets the point in V/C at which a
REJECT
battery will be rejected if it is
higher. Only enter the data to the
right of the decimal point.
(2.00 to 2.59)
Factory = 2.30
Key in data and press enter.
36. RECHARGE Allows charger to be configured
GRADE as 100D6C8, 80D6C8, or
80D6C10 rated charger.
Enter 0 = 100D6C8,
1 (B Grade) = 80D6C8,
2 (E Grade) = 80D6C10
37. FIX AH SIZE The ampere-hour size the
charger will operate at if the
charger does not detect a
BID module (0001 to nameplate
AH rating).
Factory setting = nameplate rating
38. FIX BAT TEMP The battery temperature used
for charger output voltage
compensation, if the charger
does not detect a BID module
(
32
to
132
degrees
F)
Factory Setting = 77F
39. BATTERY TYPE The battery type the charger
uses to select the proper
output voltage and current
characteristic, if the charger
does not detect a BID module.
00 FLD Flooded Lead Acid
01 CTM Custom curve (programmable)
02 YGR Sealed battery curve
03 SLR Sealed battery curve
04 DSG Sealed battery curve
05 SLE Sealed battery curve
08 MAX Opportunity Charge curve
40. START A/100AH The custom output curve
start current setting.
(10.0 to 16.3A/100AH)
Factory setting = 16.3
41. FINISH A/100AH The custom output curve
finish current setting.
(0.0 to 7.9A/100AH)
Factory setting = 4.5
42. GAS V/C The custom output curve
gassing voltage level setting.
(2.00 to 2.99V/Cell)
Factory setting = 2.40
43. LID. V/C
The custom output curve lid
voltage level setting.
(2.00 to 2.99V/Cell)
Factory setting = 2.70
44. CHARGER I.D. The battery charger
identification number. This
must be set to 0000 unless
the battery charger is part of
a CDAC system (0000 to
9999) or approval defeat DIP
switch is set, see SCR2000
features.
Factory setting = 0000
Key in data and press enter.