Screen Example
Screen Description
The Centurion Plus Heat disinfection device uses
an SD card to store the data recorded during
disinfection cycles. The green indicator light will
appear when this SD card is inserted and ready to
accept data.
SD Card Safe to Eject
When the green indicator light is displayed, the
SD card may be safely ejected from the controller.
Internal Battery Status
When the internal battery for the PLC falls below
an acceptable voltage, the indicator light will go
out. When the light goes out, the low battery
alarm will be activated. When this alarm is active,
the battery must be replaced in order for the PLC
real time clock to be maintained. See Section
10.5 for information on the battery.
Temp Maintain On/Off
This toggle will allow the user to enable
temperature maintain mode. When enabled, this
mode will prevent the device from automatically
sending hot water to the HD machine upon
achieving the disinfection set-point temperature.
The user will be prompted with a button on the
display that will send the hot water to the HD
machine.
NOTE:
This mode SHOULD NOT be enabled with
storage mode. If it is enabled, the device will
never send water to the HD machine.
Warning:
Ejecting the SD card when the green
light is not active may cause damage to the SD
card.
Schedule Menu/Storage Mode
This settings page will be displayed upon pressing
the “schedule” button in the Settings menu. This
menu will allow the user to set a scheduled time
for a disinfection.
Day of the Week (Sunday – Saturday)
Pressing on each day of the week will prompt the
user with a set time for disinfection as well as the
time when hot water will be available based on
the “Preheat Period” setting. Activating each day
of the week will change the color to a darker grey
indicating that a disinfection will occur on this
day.
Summary of Contents for 000-HS120
Page 2: ......
Page 24: ...22 098 0007 Rev B Right Side...
Page 25: ...23 098 0007 Rev B Left Side Top with top panel and controller removed...
Page 27: ...25 098 0007 Rev B 6 3 Flow Schematic 6 3 1 Standby Mode...
Page 28: ...26 098 0007 Rev B 6 3 2 Preheat Mode...
Page 29: ...27 098 0007 Rev B 6 3 3 Dispensing Mode...
Page 30: ...28 098 0007 Rev B 6 3 4 Drain Mode...
Page 68: ...66 098 0007 Rev B 13 SPARE PART LISTING 13 1 Exploded View...
Page 69: ...67 098 0007 Rev B...
Page 70: ...68 098 0007 Rev B...
Page 71: ...69 098 0007 Rev B...
Page 72: ...70 098 0007 Rev B...
Page 73: ...71 098 0007 Rev B...
Page 74: ...72 098 0007 Rev B...