thErMostAt sEttInGs - ELECtronIC ControLs 

These models are equipped with an electronic control system. The 

control system senses temperature from a factory installed Immersion 

Temperature  Probe  (see  Figure  2). The  “Operating  Set  Point”  is 

adjusted to control water temperature. This is an adjustable user 

setting in the control system’s “Temperatures Menu.” This and all 

control system menus are accessed through the UIM (User Interface 

Module - see  Figure 8) located on the front panel of the water heater.

The Operating Set Point is adjustable from 90°F/42°C to 190°F/88°C. 

The factory setting is 120°F/49°C. See the Electronic Control Models 

Operation section of this manual for instructions on how to adjust 

the Operating Set Point and other user settings.

uIM (user Interface Module)

figure 8 

Set the Operating Set Point at the lowest setting which produces 

an acceptable hot water supply. This will always give the most 

energy efficient operation.

ControL systEM fEAturEs

Advanced diagnostics: 

Plain English text and animated icons display 

detailed operational and diagnostic information. LCD screen on the 

front of the water heater displays the Sequence of Operation in real 

time. Fault or Alert messages are displayed when operational problems 

occur. Advanced Service menu displays a list of possible causes for 

current Fault and Alert conditions to aid in servicing.

Economy Mode operation:

 Control system automatically lowers 

the Operating Set Point by a programmed value during user defined 

time periods. Helps reduce operating costs during unoccupied or 

peak demand periods.

Linear Sequencing:

 Banks of heating elements (3 elements per 

bank) are energized according to adjustable (1 to 20°) differential set 

points for each bank. First bank on is the last bank off. Helps reduce 

operating costs during low/moderate loads.

ControL systEM nAVIGAtIon

The UIM (User Interface Module) is located on the front cabinet of the 

Electronic Control Model water heaters. All operational information 

and user settings are displayed and accessed using the UIM. The 

UIM includes five snap acting (momentary) user input buttons; an 

Up, Down and 3 Operational Buttons.

uIM - usEr IntErfACE ModuLE

figure 9 

up & down Buttons

Used to navigate (up and down) and to select (highlight) menu items. 

Also used to adjust or change (increase/decrease, on/off, set time) 

various user settings.

operational Buttons

The 3 Operational Buttons are multifunctional. Their current function 

is defined by the text that appears above each button on the LCD 

screen. The function will change depending on what menu is currently 

displayed or what menu item is selected. When no text appears on the 

LCD screen above an Operational Button there is no function assigned.

thE dEsktoP sCrEEn

Figure 10 below shows the control system “Desktop Screen.” This 

is the default screen. If there are no active Fault or Alert conditions 

and no user input for approximately 10 minutes the control system 

will return to this screen automatically.

Model Information

Model information and menu titles are shown in the black bar at the 

top of the Desktop Screen.

tank temperature

Current  water  temperature  as  sensed  from  the  immersion 

Temperature Probe.

operating Set Point: 

Temperature at which the control system will 

maintain tank (water) temperature in the Normal Mode. This line of 

text will read 

Economy set Point

 whenever the control system is 

operating in the Economy Mode.

Status: 

The  Operating  State  of  the  control  system  is  displayed 

beneath the Operating Set Point.

figure 10 

ELECtronIC ControL ModELs oPErAtIon

Summary of Contents for ITCE31-119

Page 1: ...eference COMMERCIAL ELECTRIC WATER HEATERS Thank you for buying this energy efficient water heater We appreciate your confidence in our products MODELS STCE31 50 80 119 ITCE31 50 80 119 INSTALLATION O...

Page 2: ...testing or replacement of gas piping or b the connection installation testing repair or servicing of appliances and equipment that is experienced in such work that is familiar with all precautions req...

Page 3: ...y may also cause erratic control system operation on ELECTRONIC CONTROL models This water heater must be connected to a grounded metal permanent wiring system or an equipment grounding conductor must...

Page 4: ...ey Road Cleveland OH 44131 3 If after reading this manual you have any questions or do not understand any portion of the instructions call the toll free number listed on the back cover of this manual...

Page 5: ...109 98 89 82 76 70 27 92 151 369 276 221 184 158 138 123 111 101 92 85 79 30 102 390 410 307 246 205 176 154 137 123 112 102 95 88 36 122 868 492 369 295 246 211 184 164 148 134 123 113 105 40 5 138...

Page 6: ...tional Sanitation Foundation NSF 5 requirements LISTED 22U1 No OF WATTS PHASE VOLTS AC ELEMENTS EACH RATED MEASURED WATTS COMMERCIAL STORAGE TANK WATER HEATER MODEL NUMBER SERIAL NUMBER ITEM ID PART N...

Page 7: ...7 FEATURES AND COMPONENTS ELECTRONIC CONTROL MODELS Figure 2...

Page 8: ...8 FEATURES AND COMPONENTS SURFACE MOUNT CONTROL MODELS Figure 3...

Page 9: ...tank or connections will not result in damage to the area adjacent to the heater or to lower floors of the structure Close to the point of major hot water usage and the power supply Hot water piping a...

Page 10: ...hysically developmentally disabled If anyone using hot water in your home fits into one of these groups or if there is a local code or state law requiring a maximum water temperature at the hot water...

Page 11: ...the building Shall not have any valve or other obstruction between the relief valve and the drain The temperature pressure relief valve must be manually operated at least once a year Caution should be...

Page 12: ...protection and disconnect switch The water heater should be grounded in accordance with national and local codes Voltage applied to the heater should not vary more than 5 to 10 of the model and rating...

Page 13: ...element current sensors for monitoring the power circuits Refer to the control circuit label on the water heater for details The CCB is powered by a small 120V 24V transformer The control circuit oper...

Page 14: ...14 CCB CENTRAL CONTROL BOARD CONTROL CIRCUIT DIAGRAM ELECTRONIC CONTROL MODELS Figure 6 WIRING DIAGRAMS...

Page 15: ...the heater circuits and includes wiring diagrams All heater circuits are designed for 60 50 hertz alternating current The water heater circuit wiring is 12 AWG AWM or TEW type rated 600 volts 105 C F...

Page 16: ...to terminal L1 with black wires 3 Reconnect all yellow wires to terminal L2 with red wires 4 Connect incoming power to terminals L1 and L2 CONVERSION TO THREE PHASE When heater is shipped for connect...

Page 17: ...page 8 The following describes the heater circuits and includes wiring diagrams All heater circuits are designed for 60 50 hertz alternating current The water heater circuit wiring is 12 AWG AWM or T...

Page 18: ...nect all red wires to terminal L2 with yellow wires 5 Connect incoming power to terminals L1 and L2 CONVERSION TO THREE PHASE When heater is shipped for connection to a single phase electrical service...

Page 19: ...Models only 4 Turn on the electrical disconnect switch 5 Observe the operation of the electrical components during the first heating cycle Use care as the electrical circuits are energized 6 Close the...

Page 20: ...ed in this instruction manual are equipped with adjustable thermostat controls to control water temperature Hot water temperatures required for automatic dishwasher and laundry use can cause scald bur...

Page 21: ...djustable 1 to 20 differential set points for each bank First bank on is the last bank off Helps reduce operating costs during low moderate loads CONTROL SYSTEM NAVIGATION The UIM User Interface Modul...

Page 22: ...control system has initiated heating operation Heating elements icon for a water heater equipped with 1 Bank of heating elements Each circle represents one heating element Each diagonal row of 3 elem...

Page 23: ...played in this menu Economy Mode Setup Seven day 24 hour time clock with temperature set back capability to reduce operating costs during unoccupied or reduced demand periods Alarm Output Setup The co...

Page 24: ...g This can improve the precision of temperature control in the storage tank and at points of use This feature can also be used to compensate for building recirculation loops hot water returning to the...

Page 25: ...on off status of each Bank of heating elements Yes On No Off Alarm Condition Displays the status of the user definable Alarm Output function see Alarm Output Setup Menu Yes alarm condition has been m...

Page 26: ...tional Buttons on the display changes as you navigate through the various menus and screens Use the Up Down buttons to select highlight in black the Economy Mode Setup menu from the Main Menu Press th...

Page 27: ...ges to ACCEPT CANCEL when the adjustment mode is activated and how the current setting is outlined rather than highlighted in black Press the Operational Button underneath ACCEPT to enter and confirm...

Page 28: ...Up Down and CHANGE buttons to enter the Mon sub menu Use the Up Down buttons to select highlight in black the Normal Operation Between setting Press the Operational Button underneath SELECT to change...

Page 29: ...n current tank temperature drops below programmable Alarm SP Fault or Alert Used for external notification whenever a Fault or Alert condition is active Fault Used for notification whenever a Fault co...

Page 30: ...sages in chronological order in this menu The most recent will be at the top of the list A time stamp is displayed below each listed Fault and Alert message showing when the Fault or Alert condition o...

Page 31: ...Restore Factory Defaults menu General Periodically the drain valve should be opened and the water allowed to run until it flows clean This will help to prevent sediment buildup in the tank bottom Peri...

Page 32: ...om water system Check for any leaks and immediately correct any if found 7 Restart the water heater as directed in this manual See the Repair Parts Illustration for anode rod location FLUSHING the Wat...

Page 33: ...not remove these types of scale which are occasionally encountered Call the toll free phone number on the back cover of this Instruction Manual to purchase UN LIME and heating element gaskets Other sc...

Page 34: ...are normal however the tank bottom and elements should be cleaned See the Maintenance section of this manual 2 Some of the electrical components of the water heater make sounds which are normal Conta...

Page 35: ...ters tank insert Q Tip or similar absorbent material between jacket opening and valve to swab spud area Remove valve if leak is indicated and repair with pipe joint compound Water on the side of the t...

Page 36: ...ELECTRIC 1 UNIT LEGEND TEMPERATURE PRESSURE RELIEF VALVE PRESSURE RELIEF VALVE CIRCULATING PUMP TANK TEMPERATURE CONTROL DRAIN FULL PORT BALL VALVE TEMPERATURE GAGE WATER FLOW SWITCH CHECK VALVE WARNI...

Page 37: ...hermostat should be set 5 degrees F higher than the Tank Temperature Control COMMERCIAL ELECTRIC 1 UNIT WITH VERTICAL STORAGE TANK LEGEND TEMPERATURE PRESSURE RELIEF VALVE PRESSURE RELIEF VALVE CIRCUL...

Page 38: ...g thermostat should be set 5 degrees F higher than the Tank Temperature Control COMMERCIAL ELECTRIC 1 UNIT WITH HORIZONTAL STORAGE TANK LEGEND TEMPERATURE PRESSURE RELIEF VALVE PRESSURE RELIEF VALVE C...

Page 39: ...LEGEND TEMPERATURE PRESSURE RELIEF VALVE PRESSURE RELIEF VALVE CIRCULATING PUMP TANK TEMPERATURE CONTROL DRAIN FULL PORT BALL VALVE TEMPERATURE GAGE WATER FLOW SWITCH CHECK VALVE WARNING THIS DRAWING...

Page 40: ...5 degrees F higher than the Tank Temperature Control COMMERCIAL ELECTRIC 2 UNITS WITH VERTICAL STORAGE TANK LEGEND TEMPERATURE PRESSURE RELIEF VALVE PRESSURE RELIEF VALVE CIRCULATING PUMP TANK TEMPERA...

Page 41: ...et 5 degrees F higher than the Tank Temperature Control COMMERCIAL ELECTRIC 2 UNITS WITH HORIZONTAL STORAGE TANK LEGEND TEMPERATURE PRESSURE RELIEF VALVE PRESSURE RELIEF VALVE CIRCULATING PUMP TANK TE...

Page 42: ...SURE RELIEF VALVE PRESSURE RELIEF VALVE CIRCULATING PUMP TANK TEMPERATURE CONTROL DRAIN FULL PORT BALL VALVE TEMPERATURE GAGE WATER FLOW SWITCH CHECK VALVE WARNING THIS DRAWING SHOWS SUGGESTED PIPING...

Page 43: ...the Tank Temperature Control COMMERCIAL ELECTRIC 3 UNITS WITH VERTICAL STORAGE TANK LEGEND TEMPERATURE PRESSURE RELIEF VALVE PRESSURE RELIEF VALVE CIRCULATING PUMP TANK TEMPERATURE CONTROL DRAIN FULL...

Page 44: ...an the Tank Temperature Control COMMERCIAL ELECTRIC 3 UNITS WITH HORIZONTAL STORAGE TANK LEGEND TEMPERATURE PRESSURE RELIEF VALVE PRESSURE RELIEF VALVE CIRCULATING PUMP TANK TEMPERATURE CONTROL DRAIN...

Page 45: ...RE RELIEF VALVE CIRCULATING PUMP TANK TEMPERATURE CONTROL DRAIN FULL PORT BALL VALVE TEMPERATURE GAGE WATER FLOW SWITCH CHECK VALVE WARNING THIS DRAWING SHOWS SUGGESTED PIPING CONFIGURATION AND OTHER...

Page 46: ...ntrol COMMERCIAL ELECTRIC 4 UNITS WITH VERTICAL STORAGE TANK LEGEND TEMPERATURE PRESSURE RELIEF VALVE PRESSURE RELIEF VALVE CIRCULATING PUMP TANK TEMPERATURE CONTROL DRAIN FULL PORT BALL VALVE TEMPERA...

Page 47: ...Control COMMERCIAL ELECTRIC 4 UNITS WITH HORIZONTAL STORAGE TANK LEGEND TEMPERATURE PRESSURE RELIEF VALVE PRESSURE RELIEF VALVE CIRCULATING PUMP TANK TEMPERATURE CONTROL DRAIN FULL PORT BALL VALVE TE...

Page 48: ...Inlet and outlet size 1 1 2 THREE HEATERS Tank Capacity Gallons Part Number H W D A 52 9003430205 66 1 4 91 3 4 27 1 4 13 1 4 80 9003430205 70 1 2 95 1 4 31 1 4 9 3 4 120 9003430205 73 1 4 99 1 2 35...

Page 49: ...9005721215 10 Nipple T P valve extension 9005717215 9005717215 9005717215 11A T P Valve 3 elements 9005715205 9005715205 9005715205 11B T P 6 or 9 elements 9005923205 9005923205 9005923205 12A Fuse P...

Page 50: ...05 9005009205 5B Fuse Block Power Circuit for 54KW at 208V model 9005079205 9005079205 9005079205 5C Fuse Block Power Circuit for 575V models 9005007205 9005007205 9005007205 6 Element Gasket BOX OF 5...

Page 51: ...y the heater is connected to unless an effective method of controlling thermal expansion is also installed at the heater s and operational at all times The relief valve installed on the heater is not...

Page 52: ...52 Technical Support and Parts 800 456 9805 www americanwaterheater com...

Reviews: