background image

5

5

III.  Electrical Connections

75

60

50

43

37

N/R

N/R

N/R

N/R

N/R

N/R

N/R

N/R

118

95

79

68

59

53

47

N/R

N/R

N/R

N/R

N/R

N/R

188

150

125

107

95

83

75

68

63

58

54

N/R

N/R

301

241

201

172

150

134

120

109

100

93

86

80

75

471

376

314

269

235

209

188

171

157

145

134

125

118

N/R = NOT RECOMMENDED

Wire ampacity and voltage drop calculation based on copper conductors with  75 degree C insulation per
1996 National Electrical Code (NEC)  Conductors in  86 degree F ambient. 
See NEC for ampacity derating for higher ambients.

27.5

30

12.5

15

17.5

20

MAXIMUM ALLOWABLE WIRE LENGTH IN FEET TO LIMIT VOLTAGE DROP TO 2%

10

MINIMUM CIRCUIT AMPACITY OF OUTDOOR UNIT (MCA)

40

32.5

35

37.5

WIRE SIZE 

(AWG)

22.5

25

6

14
12
10

8

Table 1

WARNING

To avoid the risk of fire or equipment
damage, use only copper conductors.

WARNING

Undersized wires can cause poor
equipment performance, equipment
damage, or fire.  Consult the NEC, CEC or
a qualified electrician for proper wire size.

  NOTE:  Local codes usually require that a disconnect
  switch be located near the unit.  Do not locate the
  disconnect switch on the unit itself.

WARNING

To avoid personal injury, shock, or death,
be sure wiring to the unit is properly
grounded.

1. Wire size is important to ensure proper unit operation.

Wire size must be sufficient to carry the minimum
circuit ampacity listed on the unit serial data plate.  We
recommend sizing the wires to limit the voltage drop to
a maximum of 2% from the main breaker or fuse panel
to the outdoor unit.  Use Table 1 as a guide for wire
gauge and length of run.

2. Route the power supply and ground wires through the

high voltage entrance in the unit.  Connect the power
supply wires to the contactor. Connect the ground wire
to the ground lug.

3. Route the low voltage wiring through the low voltage

entrance in the unit.  Connect the low voltage wires to
the terminal strip.

4. If an Amana approved room thermostat is not already

present, install one at a suitable indoor location.  Con-
sult the instructions packaged with the thermostat for

NOTE: This table is provided as a guide only.  Wire
sizing may be regulated by local codes.  Local inspection
is the final authority on wire sizing.

WARNING

To avoid personal injury, shock, or death,
open the electrical disconnect switch
before electrically connecting the unit.
Wiring must conform with National
Electrical Code (NEC) or Canadian
Electrical Code (CEC) and all local codes.

The wiring diagram for this unit can be found on the control
box cover. Refer to Figure 3 for field wiring connections.

START CAP
(if present)

START RELAY
(if present)

FIELD WIRING
HIGH VOLTAGE CONNECTION

FIELD WIRING
LOW VOLTAGE CONNECTION

GROUND LUG

W

Y

C

R

O

RUN CAP

DEFROST
BOARD

F

H

C

L2

L1

T1

T2

CC

PS1

RV

DFS

Figure 3

Summary of Contents for RHA**B*A

Page 1: ...The precautions listed in this Installation Manual are intended as supplemental to existing practices However if there is a direct conflict between existing practices and the content of this manual th...

Page 2: ...vice this unit 2 Install the system in accordance with all local codes If no local codes exist follow National Codes NEC in the U S CEC in Canada 3 Open the electrical disconnect switch before electri...

Page 3: ...ant Piping REFRIGERANT LINE SIZING See unit Specification Sheet for required line sizes Be sure to use the correct size as using smaller vapor lines can decrease unit performance These sizes are suita...

Page 4: ...lve to the thermocouple vacuum gauge Close the valve to the vacuum pump Shut off the pump LEAK TESTING WARNING To avoid the risk of fire or explosion never useoxygen highpressureairorflammable gasses...

Page 5: ...ze must be sufficient to carry the minimum circuit ampacity listed on the unit serial data plate We recommend sizing the wires to limit the voltage drop to a maximum of 2 from the main breaker or fuse...

Page 6: ...700 Used refrigerant may cause compressor damage and will void the warranty Most portable machines cannot clean used refrigerant well enough to meet this ARI Standard IMPORTANT If adding refrigerant t...

Page 7: ...70 80 90 100 110 120 6 8 10 12 14 16 18 20 22 24 26 28 30 32 34 36 SUPERHEAT O D UNIT OUTDOOR TEMPERATURE DESIRED SUPERHEAT vs OUTDOOR TEMPERATURE 90 F Indoor 7 0 F I n d o o r 75 F Indoor 80 F Indoor...

Page 8: ...oil is determined by both coil temperature and compressor run time See the Specification Sheet for factory settings Adjustment can be changed as required There are 30 60 and 90 minute settings availab...

Page 9: ...llow the instructions in the accessory kit s installation instructions 2 For thermostat models D9945804 and D9807605 jumper Y and W1 at the thermostat WARNING To avoid personal injury shock or death d...

Page 10: ...normal 15 Check the amperage on the indoor blower motor Is it within the limits shown on the nameplate of the motor 16 Are all access panels installed and secured 17 Do controls function properly Are...

Reviews: