background image

4

1. Connect the vacuum pump, high vacuum manifold

set, thermocouple vacuum gauge and charging cyl-
inder as shown in Figure 2.  Be sure all valves are
fully closed.

2. Confirm proper pump and gauge operation.  Open

the shutoff valve leading to the vacuum pump (C).
Start the pump. When the gauge manifold (low side)
reading drops to about 29 inches of vacuum, open
the valve to the thermocouple vacuum gauge (D).
Continue evacuation until the gauge reads 250 mi-
crons or less.

A.  HIGH SIDE VALVE
B.  LOW SIDE VALVE
C.  VACUUM PUMP
D.  THERMOCOUPLE GAUGE
E.  MANIFOLD GAUGE
F.  CHARGING CYLINDER

C

A

B

E

D

HIGH VACUUM PUMP

LARGE DIAMETER

BRAIDED VACUUM

HOSES

TO

RELATED

GAUGE

PORTS OF 

COND. UNIT

HIGH VACUUM

MANIFOLD

LOW SIDE

GAUGE

HIGH SIDE

GAUGE

DIAL-A-CHARGE

CHARGING CYLINDER

THERMOCOUPLE
VACUUM
GAUGE

F

Figure 2

3. To avoid potential gauge damage due to “pegging

the meter”, close the valve to the thermocouple
vacuum gauge (D).

4. Open the high side (B) and low (A) side valves on the

manifold gauge. Keeping the valve on the charging
cylinder closed (F), open the valve on the manifold
gauge (E) leading to the cylinder.

5. Evacuate the system to about 29 inches of vacuum

as measured by the manifold gauge (low side).

6. Open the valve to the thermocouple vacuum gauge

(D) and evacuate until the gauge reads 250 microns
or less.

7. Close the valve to the vacuum pump. Wait five

minutes, then check the pressure on the thermo-
couple vacuum gauge:

a. If the pressure is not more than 1500 microns, the

system is leak-free and properly evacuated. Pro-
ceed to Step 8.

b. If the pressure rises, but holds at about 5000

microns, moisture and noncondensables are still
present. Open the valve to the
vacuum pump, and go back to Step 6.

c. If the pressure rises above 5000 microns, a leak is

present. Repeat Section II, 

Leak Testing.

8. Close the valve to the thermocouple vacuum gauge.

Close the valve to the vacuum pump. Shut off the
pump.

LEAK TESTING

WARNING

To avoid the risk of fire or explosion, never
use oxygen, high pressure air or flammable
gasses for leak testing of a refrigeration
system.

1. Be sure both hand valves on the gauge manifold are

closed relative to the center port (i.e., turned in all the
way.) Attach this gauge manifold to the service valves
on the unit.  Do not open the unit service valves.  Do
not use refrigerant from the unit for leak testing - it has
been precisely measured at the factory for optimum
performance.

WARNING

To avoid possible explosion, the line from
the nitrogen cylinder must include a
pressure regulator and a pressure relief
valve.  The pressure relief valve must be
set to open at no more than  150  psig.

2. Connect a cylinder of dry nitrogen to the center port on

the gauge manifold.

3. Open the hand valve a minimal amount on the line

coming from the nitrogen cylinder.

4. Open the high pressure valve on the manifold gauge.

Pressurize the refrigerant lines and the indoor coil to
150 psig (1034 kPA).  To reach 150 psig, you may
need to further open the hand valve on the nitrogen
cylinder.  Once 150 psig has been reached, close the
valve on the nitrogen cylinder and disconnect it from
the manifold gauge.

WARNING

To avoid possible explosion or equipment
damage, do not exceed 150 psig when
pressure testing.

5. Place a soapy solution on all connections and joints

and check for bubbles.  If bubbles are seen, you have
a leak.  Mark these locations.

NOTE:  If you plan to use an electronic leak detector,
add a trace of R-22 to the system (if permitted by

current EPA regulations).

6. Using the manifold gauge, carefully release the nitro-

gen from the system.  Check for leaks.  If leaks are
found, repair them and repeat steps 1 through 6.  If no
leaks are found, proceed to system evacuation.

SYSTEM EVACUATION

NOTE: Evacuate the indoor (ID) coil and line sets prior to
releasing charge from the outdoor (OD) unit into the system.

Summary of Contents for RHA**B*A

Page 1: ...The precautions listed in this Installation Manual are intended as supplemental to existing practices However if there is a direct conflict between existing practices and the content of this manual th...

Page 2: ...vice this unit 2 Install the system in accordance with all local codes If no local codes exist follow National Codes NEC in the U S CEC in Canada 3 Open the electrical disconnect switch before electri...

Page 3: ...ant Piping REFRIGERANT LINE SIZING See unit Specification Sheet for required line sizes Be sure to use the correct size as using smaller vapor lines can decrease unit performance These sizes are suita...

Page 4: ...lve to the thermocouple vacuum gauge Close the valve to the vacuum pump Shut off the pump LEAK TESTING WARNING To avoid the risk of fire or explosion never useoxygen highpressureairorflammable gasses...

Page 5: ...ze must be sufficient to carry the minimum circuit ampacity listed on the unit serial data plate We recommend sizing the wires to limit the voltage drop to a maximum of 2 from the main breaker or fuse...

Page 6: ...700 Used refrigerant may cause compressor damage and will void the warranty Most portable machines cannot clean used refrigerant well enough to meet this ARI Standard IMPORTANT If adding refrigerant t...

Page 7: ...70 80 90 100 110 120 6 8 10 12 14 16 18 20 22 24 26 28 30 32 34 36 SUPERHEAT O D UNIT OUTDOOR TEMPERATURE DESIRED SUPERHEAT vs OUTDOOR TEMPERATURE 90 F Indoor 7 0 F I n d o o r 75 F Indoor 80 F Indoor...

Page 8: ...oil is determined by both coil temperature and compressor run time See the Specification Sheet for factory settings Adjustment can be changed as required There are 30 60 and 90 minute settings availab...

Page 9: ...llow the instructions in the accessory kit s installation instructions 2 For thermostat models D9945804 and D9807605 jumper Y and W1 at the thermostat WARNING To avoid personal injury shock or death d...

Page 10: ...normal 15 Check the amperage on the indoor blower motor Is it within the limits shown on the nameplate of the motor 16 Are all access panels installed and secured 17 Do controls function properly Are...

Reviews: