M0309_N_Series_ABS_700-3kVA_User_Manual V2.8 2012-06-12
19
7.
Audible Alarm
7.1.
Backup mode
The UPS will beep once every five (5) seconds and the BACKUP LED will light,
when the unit is in back-up mode.
(beep - - - - beep - - - - beep) [Slow beep]
7.2.
Low Battery
The UPS will beep twice every five (5) seconds and the BACKUP LED will flash,
when the batteries are almost depleted.
(beep - beep - beep) [Fast beep]
7.3.
Bypass
The UPS BYPASS LED will illuminate. The UPS will not beep.
7.4.
Fault
The UPS will sound a continuous beep and the FAULT LED will illuminate and the
LCD will display the cause.
(beeeeep) [Continuous beep]
8.
Battery Maintenance
•
On initial start-up it is recommended the batteries have a minimum of eight (8) hours of
charging to ensure proper operation.
•
During normal operation of the UPS, the charge level of the batteries will be maintained
automatically.
•
The typical recharge time to 90% from 0% charge level is 6-8 hours
•
Under normal operating conditions, the supplied batteries are expected to last
approximately five (5) years, or 200 discharges, from date of receipt.
•
Refer to the purchase date you recorded in this manual if you suspect that the batteries
have been exhausted.
•
If the UPS is to remain in storage for an extended period of time, it is strongly
recommended that the UPS be powered up for a period of twenty-four (24) hours, every
three (3) months, to recharge the batteries and prevent premature failure.
9.
Environmental Protection
The UPS incorporates sealed maintenance free lead-acid batteries. When replacing the
batteries, the defective batteries must be disposed of carefully to prevent any risk of
environmental pollution by the harmful products they contain (lead and acid). Please refer to
local and regional environmental codes when disposing of the batteries.