Always
O
n UPS Systems
4.2.
Electrical Considerations
The UPS shall be installed by a qualified technician and wired in accordance with
local and national electrical codes.
The following information is for recommendation only.
Standard Load
VA Rating
F (Hz)
Panel
Breaker Size
Input Output
Voltage Current
Voltage Current
700VA/490W
700VA (110)
50/60
15A
87-140Vac
9A max
120V
5A
1000VA/700W
1000VA (110)
50/60
15A
80-138Vac
12A max
120V
8.3A
1000VA/700W
1000VA (220)
50/60
15A
160-276Vac
6A max 208/220 4.8A/4.55A
1500VA/1050W 1500VA (110)
50/60
15A
80-138Vac
18A max
120V
12.5A
1500VA/1050W 1500VA (220)
50/60
15A
160-276Vac
9A max 208/220
6.2A
2000VA/1400W 2000VA (110)
50/60
20A
80-138Vac 20.3A max
120V
12.6A
2000VA/1400W 2000VA (220)
50/60
15A
160-276Vac 10.2A max 208/220 9.61A/9.1A
3000VA/2100W 3000VA (110)
50/60
30A
80-138Vac 30.5A max
120V
24.9A
3000VA/2100W 3000VA (220)
50/60
20A
160-276Vac 14.7A max 208/220 14.4A/13.6A
Table 4.2.1
Electrical information for proper installation, breaker and cable ratings
4.3.
Rear View Diagrams
Interface
(optional)
EPO
Rs232/Dry Contact
Inerface
Network
Transient
Protec tor
Circuit
Breaker
Input
Outlet
USB
External
Battery
(optional)
Interface
(optional)
EPO
Rs232/Dry Contact
Inerface
Network
Transient
Protec tor
Circuit
Breaker
Input
Outlet
USB
External
Battery
(optional)
M0309_N_Series_ABS_700-3kVA_User_Manual V2.8 2012-06-12
10
Figure 4.3.1
Rear view of the 700VA, 1kVA, 1.5kVA UPS 120VAC
Figure 4.3.2
Rear view of the 700VA, 1kVA, 1.5kVA UPS 220VAC