4.0 Operation
4.1 Start-up and Test
4.1.1 AC Line Operation
Before making power supply connections, verify the correct voltage, polarity and
1.
frequency are available from both the AC utility power source and the DC battery
system.
Verify the AC circuit breaker (on the customer supplied service disconnect) and
2.
the battery switch on the XM2-300HP are off.
Plug the XM2-300HP power cord into the convenience outlet and connect the
3.
battery cable to the CableUPS. Plug the RTS into the temp probe connection
and attach it to the negative terminal of the battery. Refer to Fig. 1-8. Plug the
LRI cables into the front panel, if applicable.
Switch the AC (service disconnect) circuit breaker on to start initial power
4.
up. During this stage the power supply performs a “display test” and verifies
configuration for the power supply. After the initial display test, a “No Batteries”
alarm message appears in the Smart Display because the battery switch is off.
The green output LED remains off and the red alarm LEDcontinues to flash
while in this alarm state (see Section 4.5).
Access the configuration screen any time by simultaneously pressing UP and ENTER.
NOTE: