4.1
Start-up and Test, continued
4.1.1 AC Line Operation, continued
Use the Smart Display to verify XM2-300HP operations. If desired, the No Battery
5.
alarm can be disabled by changing Battery Capacity to “0” in the setup menu.
Use the Smart Display to verify AC output (±5%).
6.
4.1.2 Self Test Operation
The XM2-300HP should be operating correctly with no alarms present. Use the
1.
Smart Display to verify Normal and/or Additional Information (Communication In
-
formation available only when DPM is installed). Verify test duration in the Setup
Menu as needed.
Press and hold DOWN and ENTER simultaneously to start Self Test. The test will
2.
run for a preset time (5-180 minutes, set in the Setup Menu). Self Test can also
be entered by setting Self Test to ON in the Setup Menu.
While in self test mode, use the Smart Display or a true RMS voltmeter to verify
3.
output at the module’s AC Output. Output voltages should appear within ±5% of:
87Vac for 90V units, 63Vac for CE units, and 60Vac for 60V units at nominal line
input voltage.
To cancel a self test in progress, push and hold DOWN and ENTER a second
4.
time, or change Self Test to OFF in the Setup Menu.
Switch on the battery switch. Within one minute the flashing red alarm LED turns
7.
off, the green output LED turns on, the No Battery alarm clears and the power
supply displays Operations Normal. Use the Smart Display to verify operations
and setup as needed.
Setting
Low (-5%)
High (+5%)
87Vac (Domestic models)
82.65Vac
91.35Vac
60Vac (Domestic models)
57.0Vac
63.0Vac
63Vac (CE models)
59.85Vac
66.15Vac
Table 4-1, AC Output
33
017-877-B1-001 Rev. A