32
Alpha E-Tec 25R - Commissioning
ID
Parameter
Description
Range
9 - 20
(x 100 rpm)
30 - 70
(x 100 rpm)
S0 - S3
(x 100 rpm)
S2 - S1
(x 100 rpm)
15 - 40
(x 100 rpm)
20 - 50 °C
(S5+5) - 80 °C
-9 to +9 °C
Defines the operating speed of the fan at minimum DHW output
Defines the operating speed of the fan at maximum DHW output
Defines the operating speed of the fan at minimum CH output
Defines the operating speed of the fan at maximum CH output
Defines the operating speed of the fan during the ignition phase
Defines the minimum flow temperature set point
Defines the maximum flow temperature set point
If the reading of the external sensor is not correct it is possible to
adjust the reading to correlate with the true outside value
DHW minimum
no. of fan revs
DHW maximum
no. of fan revs
CH minimum
no. of fan revs
CH maximum
no. of fan revs
Ignition phase
no. of fan revs
CH set point
min. temperature
CH set point
max. temperature
External sensor
S0
S1
S2
S3
S4
S5
S6
S7
Default
NG = 14
LPG = 13
NG = 60
LPG = 57
NG = 14
LPG = 13
NG = 53
LPG = 49
28
25
80
0
ID
Parameter
Description
Range
0
0
0 - 1
0
0
0
0 - 1
0 - 1
Not used on this model. This parameter value is fixed on 0
Not used on this model. This parameter value is fixed on 0
The external pump can function in two ways
0 Intermittent
- The pump is controlled according to the heating
request of a room thermostat or remote control
1 Continuous
- In 'Winter' mode the pump runs continuously
Not used on this model. This parameter value is fixed on 0
Not used on this model. This parameter value is fixed on 0
Not used on this model. This parameter value is fixed on 0
0
- Off
1
- On
0
- with external 230V DHW request signal (optional relay board
is necessary)
1
- with optional Alpha diverter valve kit (and cylinder sensor).
-
-
Pump functioning
(optional)
-
-
-
Frost protection
Cylinder
management
P0
P1
P2
P3
P4
P5
P6
P7
Default
0
0
0
0
0
0
0
0