PIN #
NAME
TYPE
FUNCTION
7
REMOTE
BYPASS
INPUT #3
By connecting pin 7 to pin 15 the load power supply
switches from inverter to bypass. For as long as the
connection remains, the TRI POWER X33 HE keeps
operating from the bypass, even if the input mains
voltage is absent. If the jumper is removed in presence
of the mains voltage, the TRI POWER X33 HE
resumes operating from the inverter. If the jumper is
removed in absence of the mains voltage, the TRI
POWER X33 HE resumes operating
from the battery
4,5,12
BATTERY LOW
OUTPUT #1
Indicates that the batteries are about to run out when
contact 5/12 is closed (1)
6,13,14
BATTERY
WORKING
OUTPUT #2
Indicates that the TRI POWER X33 HE is running on
battery power when
contact 6/14 is closed
9,10
LOCK
OUTPUT #3
When the contact is closed, indicates that the TRI
POWER X33 HE is
locked (1)
3,11
BYPASS
OUTPUT #4
When the contact is closed, indicates that the load is
powered via the bypass
N.B.:
The figure shows the contacts present inside the TRI POWER X33 HE, which are capable of carrying a max.
current of 0.5A to 42Vdc.
The position of the contact indicated in the figure is with no alarm or signal present.
(1)
The output may be programmed using the configuration software. The function indicated is selected by default (factory setting)