After a few seconds, check that the display is turned on and that the TRI
POWER X33 HE enters STAND-BY mode.
If an error message appears on display indicating a wrong cyclic sense of the input phases, perform the following
operations:
Open all the input and output isolators
Wait for the display to turn off
Open the battery fuse holders
Open all the protections Tri Power X33 HEtream the TRI POWER X33 HE
Remove the protective panel covering the input terminal board
Correct the position of the input wires so that the cyclic sense of the phases is respected.
Only if the separate bypass option is present:
check which terminal board (input and/or bypass) the code
error shown on display corresponds to (se
e the “Alarm codes” paragraph); correct the position of the wires
following the indications on the terminal board.
Close the protective panel again
Repeat the preliminary operations given in the previous page.
Press the button to access the start-up menu. Press “YES” when
requested to confirm. press to confirm and wait for a few seconds.
Make sure that the TRI POWER X33 HE enters ON-LINE mode and
that the load is on the inverter.
Open the input isolator (SWIN) and wait for a few seconds. Check that
the TRI POWER X33 HE enters “battery working” mode and that the
load is still powered correctly. You should hear a beep about once
every 7 seconds.
Close the input isolator (SWIN) and wait for a few seconds. Make sure
that the TRI PO
WER X33 HE is not on “battery working” mode anymore
and that the load is still powered correctly by the inverter.
To set up Date and Time, access menu 8.6.7 (see “Menu display”). Use
direction buttons (
↑↓
) to set up the desired value, and the confirm button
( ) to proceed to the next menu. To save the new set up, return to
the previous menu by pressing the
button.