Required Daily Testing 

8.1. 

Required Daily Testing Before Use 

This Control system requires daily inspections before use, to confirm full functionality of all safety 

features.   Failure to do so could put an operator or bystander’s life at risk.  Be aware that all safety features 
must function as described below. If one system is not operating correctly it could have deadly consequences.  
Make sure that the reset key is controlled by ONLY the authorized person on sight.  The key allows the T4P-
GF-1U panel to be started, and reset in the case of an earth/ground fault failure.  Allowing the key to remain 
with the panel while being operated allows anyone to turn on and reset the box without authorization. Take the 
key out once the unit is started.  

This procedure will require the test plug to complete. The test plug is designed so when installed in the 

locations listed below if the switches are both in the center position all receptacles will show a green indicator 
because of the 300 ohm resisters used to simulate the pump and platens. If any switch is pushed down the plug 
will have its resistance decreased and will generate the platen indicator to indicate a red.  This will check each 
platen receptacle if done one at a time.  If either switch is pushed up it will decrease the resistance to the pump 
receptacle and generate a red indication on the pump indicator.  Any plug removed will generate a lost pilot and 
give a yellow indication. 

1.

 

Check the serial plate to confirm the voltage, amperage and phase are correct for the power being 
used. 

2.

 

Confirm that the platens being used match the power being used. 

3.

 

Confirm that the platens are GF compatible by inspecting the serial plate on the platen, (the model 
should end in GF). 

4.

 

Inspect all cables for damage, wear or unsafe conditions. If you are not familiar with what is 

safe for cords and cables get someone who is.  Think safety first.  If any of the cables are not safe 
to use contact your maintenance department and/or Shaw Almex for repair or replacement 
instructions. 

5.

 

Check the cable plugs and receptacles for signs of wear or conditions that would make them 
unsafe to use. If you are not familiar with what is safe for cords and cables get someone who is.  
Think safety first. If any of the cables are not safe to use contact your maintenance department 
and/or Shaw Almex for repair or replacement instructions. 

6.

 

Connect the main power supply cord to the appropriate receptacle and the T4P-GF-1U box.  

7.

 

Make sure the E-Stop is reset before continuing. 

8.

 

When power is ON the Test Button Fault Indicator and three phase indication lights, L1, L2, and 
L3 should be illuminated.  There should be no other lights or temperature controllers on at this 
time. 

If this doesn’t occur remove the key and lockout and tag out the unit. 

Services will be 

required. 

9.

 

Plug the test plugs into the platen and the pump receptacle, (these must be purchased with every 
order of T4P-GF-1U boxes).  Make sure the switches are in the center position.   

10.

 

Turn the reset key and the temperature controllers should turn on and indicate about 80 F or 27 C 

11.

 

At this point the green light should indicate a proper earth/ground connection. 

 If this doesn’t 

occur remove the key and lockout and tag out the unit. 

Services will be required. 

12.

 

Reset the main breaker and turn each platen switch to 

1M

 and then 

O

.  You should hear the 

contactors in the box engage and disengage. 

If this doesn’t occur remove the key and lockout 

and tag out the unit. 

Services will be required. 

13.

 

Place the test cord plug into the pump and platen receptacles. When each toggle switch is used in 
the down position it will generate a red light.  If either switch is pushed up it will generate a red 
pump indicator.  If the plugs are removed this will generate a yellow indication.  

If this doesn’t 

occur remove the key and lockout and tag out the unit. 

Services will be required. 

14.

 

Place the test cord plug into the platen receptacles. When the toggle switch is used in the center it 
generates a red. When the switch is put in one position it generates a green light on the platen 

Summary of Contents for T4PGF1

Page 1: ...This manual was prepared to present the correct methods and procedures of operating and maintaining your ALMEX GROUND FAULT CONTINUITY CHECKING TEMPERATURE CONTROLPANEL Read this manual carefully bef...

Page 2: ...l Heating 10 6 2 Temperature Control 10 7 REQUIRED DAILY TESTING 11 7 1 Required Daily Testing Before Use 11 8 MAINTENANCE 12 8 1 Opening the Control Cabinet 12 8 2 Overload Protection 12 8 3 Temperat...

Page 3: ...Overcurrent Protection Required 30 Amp 15 per platen 10 amp pump Temperature Sensor 100 platinum RTD Index of Protection with case closed IP 67 Design of Protection with case open IP 66 Ancillary Item...

Page 4: ...ply with the following in part or full where relevant AS NZS 3000 2007 Electrical Installations Australian New Zealand Wiring Rules AS NZS 3007 2013 Electrical equipment in mines and quarries Surface...

Page 5: ...ould perform all maintenance of the electrical components of the temperature control panel 2 All of the electrical components contain live circuits Do not open or service any of the electrical equipme...

Page 6: ...er Supply Connector 1REC 2 Main Breaker 1CB 3 Platen Switch x2 24 30SS 4 Platen Temperature Control x2 18 25TC 5 Platen Connector x2 5 11REC 6 Alarm over temperature audible 73ABU 7 Emergency Stop Swi...

Page 7: ...Turn the top and bottom platen switches to the 0 off position 1 Install a suitable electrical connector to the power supply cable Refer to the electrical specifications indicated on the serial plate...

Page 8: ...under 55ms If the earth fault system does not trip LOCK this box out and have it repaired immediately This should be checked every time the T4P GF system is used If the system has been tripped on its...

Page 9: ...t 2 After changing the SET VALUE Turn the RESET Switch to off then back on Failure to do this may cause the temperature to overshoot the set point Important The maximum recommended operating temperatu...

Page 10: ...emitting diode will continue to flash on and off to maintain SET VALUE temperature Start timing the cure when SET VALUE is reached 7 After the cure time turn the controller switches to the 0 off posi...

Page 11: ...ny of the cables are not safe to use contact your maintenance department and or Shaw Almex for repair or replacement instructions 5 Check the cable plugs and receptacles for signs of wear or condition...

Page 12: ...mediately VOIDS warranty SAFETY Disconnect The Power Supply 1 Remove the 8 screws around the perimeter of the face panel and carefully lift the chassis out of the case The chassis fits very closely in...

Page 13: ...AT diode will flash until auto tuning is complete After set point has been reached it may take approximately 20 minutes for the AT diode to stop flashing It is necessary to wait for the AT diode to st...

Page 14: ...nnection in cable or platen connector 1 This usually means an RTD probe is an incorrect type has failed or the signal is not getting to the temperature controller 2 This shows earth fault condition ha...

Page 15: ...instruction manual 3 Faulty relay 3 Disconnect power supply and open control cabinet Using an Ohmmeter check for continuity between terminals L and T on the suspect relay If there is continuity relay...

Page 16: ...ues Wed Thur Fri Sat Sun Complete system functionality check see Daily Prestart Inspections Sec 8 Electrical cable and cords are in good working order and not damaged Receptacle and locking clamp cond...

Page 17: ...Daily Testing Sec 8 X X X X Electrical cable and cords are in good working order and free of damage and visibly labeled check continuity of the cables X X X X Receptacle and Locking Clamp Condition I...

Page 18: ...work loads and conditions Contact Almex for instructions X X Check for proper temperature controller readings Contact Almex for instructions or have The Technician check during inspection X X Check fo...

Page 19: ...T4PGF1 INSTRUCTION MANUAL Page 19 SHAW ALMEX INDUSTRIES LIMITED June 14 2017 12 RECEPTACLE PIN EXPLANATION Platen receptacle Pump Receptacle Ground Pin Pilot Pin Power Pins Voltage Coding Pin...

Page 20: ...zation and documentation prior to returning goods to the factory The service department may be reached at the above numbers 12 3 Guarantee Your ALMEX vulcanizing equipment is guaranteed against defect...

Page 21: ...T4PGF1 INSTRUCTION MANUAL Page 21 SHAW ALMEX INDUSTRIES LIMITED June 14 2017 14 WARRANTY...

Page 22: ...960 008 Triple Fuse Holder 9FU 3 26900 026 Step Down Transformer Fuses STER 13 26728 021 Small Terminal 1 26728 025 Rail 3 1 32 Long 38340 GTER 6 26728 048 Ground Terminal TER 3 26728 040 Small Termin...

Page 23: ...Component Part Information ITEM QTY PART NO DESCRIPTION 1REC 1 26766 014 Male Inlet Plug 1 CB 1 26920 034 Breaker 1 CB 1 R6545 Aluminum Breaker Plate 1 CB 1 26373 022 Breaker Seal Cover 1 CB 2 28600 0...

Page 24: ...018 Base Pump 1 Lever 39REC 1 26772 026 Female Insert Crimp PL79 80 1 29301 016 Tri Colour Pilot Light 47PB 1 46600 026 Red Push Button Switch 47PB 1 29307 006 Base Red Light Module 47PB 1 26500 026...

Page 25: ...T4PGF1 INSTRUCTION MANUAL Page 25 SHAW ALMEX INDUSTRIES LIMITED June 14 2017 16 ELECTRICAL DRAWINGS...

Page 26: ...T4PGF1 INSTRUCTION MANUAL Page 26 SHAW ALMEX INDUSTRIES LIMITED June 14 2017...

Page 27: ...T4PGF1 INSTRUCTION MANUAL Page 27 SHAW ALMEX INDUSTRIES LIMITED June 14 2017...

Page 28: ...T4PGF1 INSTRUCTION MANUAL Page 28 SHAW ALMEX INDUSTRIES LIMITED June 14 2017...

Page 29: ...T4PGF1 INSTRUCTION MANUAL Page 29 SHAW ALMEX INDUSTRIES LIMITED June 14 2017 TEST PLUG SCHEMATICS Part 46047 004...

Page 30: ...T4PGF1 INSTRUCTION MANUAL Page 30 SHAW ALMEX INDUSTRIES LIMITED June 14 2017...

Reviews: