506725-01
Page 16 of 48
Issue 1109
TABLE 7
Maximum Allowable Intake or Exhaust Vent Length in Feet
*Size intake and exhaust pipe length separately. Values in table are for Intake OR Exhaust, not combined total.
Both Intake and Exhaust must be same pipe size.
Standard Termination at Elevation 0 − 10,000 ft.
Number
Of 90°
Elbows
Used
2" Pipe
2−1/2" Pipe
3" Pipe
Model
Model
Model
045
070
090
110
045
070
090
110
045
070
090
110
1
61
46
24
n/a
100
80
43
n/a
127
127
108
108
2
56
41
19
95
75
38
122
122
103
103
3
51
36
14
90
70
33
117
117
98
98
4
46
31
n/a
85
65
28
112
112
93
93
5
41
26
80
60
23
107
107
88
88
6
36
21
75
55
18
102
102
83
83
7
31
16
70
50
13
97
97
78
78
8
26
11
65
45
n/a
92
92
73
73
9
21
n/a
60
40
87
87
68
68
10
16
55
35
82
82
63
63
Concentric Termination Elevation 0 − 10,000 ft.
Number
Of 90°
Elbows
Used
2" Pipe
2−1/2" Pipe
3" Pipe
Model
Model
Model
045
070
090
110
045
070
090
110
045
070
090
110
1
53
38
22
n/a
90
70
39
n/a
111
111
104
104
2
48
33
17
85
65
34
106
106
99
99
3
43
28
12
80
60
29
101
101
94
94
4
38
23
n/a
75
55
24
96
96
89
89
5
33
18
70
50
19
91
91
84
84
6
28
13
65
45
14
86
86
79
79
7
23
n/a
60
40
n/a
81
81
74
74
8
18
55
35
76
76
69
69
9
13
50
30
71
71
64
64
10
n/a
45
25
66
66
59
59
A95DF / 95G1DF and A93DF / 92G1DF