Rockwell Automation Publication 5069-UM003A-EN-P - May 2018
95
Master Command List
Appendix B
Response
The addressed slave responds with its address and the function code, followed
by the information field. The information field contains 1 byte describing the
quantity of data bytes to be returned. The contents of the registers requested
(DATA) are two bytes each, with the binary content right justified within each
pair of characters. The first byte includes the high-order bits and the second,
the low-order bits.
Because the slave interface device is normally serviced at the end of the
controller's scan, the data reflect the register content at the end of the scan.
Some slaves limit the quantity of register content provided each scan; thus for
large register quantities, multiple transmissions are made using register content
from sequential scans.
In the example below, the registers 40108…40110 have the decimal contents
555, 0, and 100 respectively.
Read Input Registers (Function Code 04)
Query
This function retrieves the contents of the controller's input registers from the
Modbus 3x range. These locations receive their values from devices that are
connected to the I/O structure and can only be referenced, not altered from
within the controller. The addressing allows retrieving up to 125 registers at
each request; however, the specific slave device can have restrictions that lower
this maximum quantity. The registers are numbered for zero (30001 = zero,
30002 = one, and so on). Broadcast mode is not allowed.
The following example requests the contents of register 30009 in slave number
11.
Node Address
Function Code
Byte Count
High Data
Low Data
High Data
Low Data
High Data
Low Data
Error Check
Field
(2 bytes)
0B
03
06
02
2B
00
00
00
64
CRC
TIP
This is the structure of the message being sent out to the Modbus network.
The following byte values are in hexadecimal display.
Node Address
Function Code
Data Start Point
High
Data Start Point
Low
Data Number of
Points High
Data Number of
Points Low
Error Check Field
(2 bytes)
0B
04
00
08
00
01
CRC
Summary of Contents for 5069-SERIAL
Page 1: ...Compact 5000 I O Serial Module Catalog Number 5069 SERIAL User Manual OriginalInstructions...
Page 9: ...Rockwell Automation Publication 5069 UM003A EN P May 2018 9 Preface Notes...
Page 10: ...10 Rockwell Automation Publication 5069 UM003A EN P May 2018 Preface...
Page 88: ...88 Rockwell Automation Publication 5069 UM003A EN P May 2018 Appendix A Module Tags Notes...
Page 101: ...Rockwell Automation Publication 5069 UM003A EN P May 2018 103 Programming Example Appendix C...
Page 104: ...106 Rockwell Automation Publication 5069 UM003A EN P May 2018 Appendix C Programming Example...
Page 109: ......