60
Rockwell Automation Publication 5069-UM003A-EN-P - May 2018
Chapter 4
Configure Compact 5000 I/O Serial Module
Figure 10 - Modbus Slave Module Definition Parameters
shows definitions of the Modbus Slave configurable parameters.
IMPORTANT
On the module definition screen, you will see two options at the top for
moving the commands up and down. If either of these buttons are used,
make sure the user program is adjusted to reflect the new location of the
command or the program will show and error.
Table 14 - Modbus Slave Module Definition Parameters
Parameter
Definition
Register Type
• Disabled (default)
• Coils
• Discrete Inputs
• Input Registers
• Holding Registers
Data Type
• BOOL
• INT
• REAL
Register Start Address
• 0…65535
(default = 0)
Register Length
• Dependent on Data Type
– BOOL: 1…128
(default =1)
– INT: 1…100
(default = 1)
– REAL: 1…50
(default = 1)
Data Index
Location of data in the output or input tags depending on the register type defined.
For more information, see the following section on
.
Summary of Contents for 5069-SERIAL
Page 1: ...Compact 5000 I O Serial Module Catalog Number 5069 SERIAL User Manual OriginalInstructions...
Page 9: ...Rockwell Automation Publication 5069 UM003A EN P May 2018 9 Preface Notes...
Page 10: ...10 Rockwell Automation Publication 5069 UM003A EN P May 2018 Preface...
Page 88: ...88 Rockwell Automation Publication 5069 UM003A EN P May 2018 Appendix A Module Tags Notes...
Page 101: ...Rockwell Automation Publication 5069 UM003A EN P May 2018 103 Programming Example Appendix C...
Page 104: ...106 Rockwell Automation Publication 5069 UM003A EN P May 2018 Appendix C Programming Example...
Page 109: ......