Rockwell Automation Publication 5069-UM003A-EN-P - May 2018
Chapter 3
Compact 5000 I/O Serial Module Features
Generic ASCII Receive Methods
When receiving the ASCII packet based on a fixed number of characters, the
number of characters is configured in the Read Buffer Size parameter.
• For this method, configure Termination Mode for Ignore End
Delimiter.
When receiving the ASCII packed based on timeout since the last character
was received, the timeout in milliseconds is configured in the Message
Timeout parameter.
• For this method, configure Termination Mode for Ignore End
Delimiter.
When receiving the ASCII packed based on Termination delimiters at the end
of the packet, if termination mode is “Include”, then the termination bytes
remain appended to the end of the data copied into the ASCII.RxData input
tag. If the termination mode is “Exclude”, then the termination bytes are
stripped off.
For Generic ASCII Sample Code, see