
Rockwell Automation Publication 5069-UM003A-EN-P - May 2018
27
Compact 5000 I/O Serial Module Features
Chapter 3
Electronic Keying
Electronic Keying reduces the possibility that you use the wrong device in a
control system. It compares the device that is defined in your project to the
installed device. If keying fails, a fault occurs. These attributes are compared.
The following Electronic Keying options are available.
Carefully consider the implications of each keying option when selecting one.
More Information
For more detailed information on Electronic Keying, see Electronic Keying in
Logix 5000 Control Systems Application Technique, publication
Attribute
Description
Vendor
The device manufacturer.
Device Type
The general type of the product, for example, digital I/O module.
Product Code
The specific type of the product. The Product Code maps to a catalog number.
Major Revision
A number that represents the functional capabilities of a device.
Minor Revision
A number that represents behavior changes in the device.
Keying Option
Description
Compatible
Module
Lets the installed device accept the key of the device that is defined in the project when the
installed device can emulate the defined device. With Compatible Module, you can typically
replace a device with another device that has the following characteristics:
• Same catalog number
• Same or higher Major Revision
• Minor Revision as follows:
– If the Major Revision is the same, the Minor Revision must be the same or higher.
– If the Major Revision is higher, the Minor Revision can be any number.
Disable Keying
Indicates that the keying attributes are not considered when attempting to communicate with
a device. With Disable Keying, communication can occur with a device other than the type
specified in the project.
ATTENTION
: Be cautious when using Disable Keying; if used incorrectly, this option can lead to
personal injury or death, property damage, or economic loss.
We strongly recommend that you do not use Disable Keying.
If you use Disable Keying, you must take full responsibility for understanding whether the
device being used can fulfill the functional requirements of the application.
Exact Match
Indicates that all keying attributes must match to establish communication. If any attribute
does not match precisely, communication with the device does not occur.
IMPORTANT
Changing Electronic Keying parameters online interrupts connections to the device
and any devices that are connected through the device. Connections from other
controllers can also be broken.
If an I/O connection to a device is interrupted, the result can be a loss of data.
Summary of Contents for 5069-SERIAL
Page 1: ...Compact 5000 I O Serial Module Catalog Number 5069 SERIAL User Manual OriginalInstructions...
Page 9: ...Rockwell Automation Publication 5069 UM003A EN P May 2018 9 Preface Notes...
Page 10: ...10 Rockwell Automation Publication 5069 UM003A EN P May 2018 Preface...
Page 88: ...88 Rockwell Automation Publication 5069 UM003A EN P May 2018 Appendix A Module Tags Notes...
Page 101: ...Rockwell Automation Publication 5069 UM003A EN P May 2018 103 Programming Example Appendix C...
Page 104: ...106 Rockwell Automation Publication 5069 UM003A EN P May 2018 Appendix C Programming Example...
Page 109: ......