Compact 5000 I/O Serial Module Features
Chapter 3
Data Received from the Serial Port in Immediate Mode
After the serial port receives data, it processes the data using the following
steps.
1. The serial module receives the packet.
2. If any of the following conditions occur, the serial module creates a
record.
a. Message Timeout timer expires.
b. The number of received bytes equals the configured Read Buffer Size.
c. Termination Delimiter bytes were received.
3. The serial module copies the data into the ASCII.RxData input tag,
copies the number of characters that are received into the
ASCII.RxDataLength input tag, increments the ASCII.RxID input tag
and sends it to the controller.
Figure 7 - Data Received from the Serial Port in Immediate Mode
Controller
Receive
Data
RPI
comes
Produce Data
Decision
Latest Record
The Latest
Record
RxBuffer
5069-SERIAL
RxFIFO
Binary
Data
Binary
Data
UART
Send
Data
Target
Summary of Contents for 5069-SERIAL
Page 1: ...Compact 5000 I O Serial Module Catalog Number 5069 SERIAL User Manual OriginalInstructions...
Page 9: ...Rockwell Automation Publication 5069 UM003A EN P May 2018 9 Preface Notes...
Page 10: ...10 Rockwell Automation Publication 5069 UM003A EN P May 2018 Preface...
Page 88: ...88 Rockwell Automation Publication 5069 UM003A EN P May 2018 Appendix A Module Tags Notes...
Page 101: ...Rockwell Automation Publication 5069 UM003A EN P May 2018 103 Programming Example Appendix C...
Page 104: ...106 Rockwell Automation Publication 5069 UM003A EN P May 2018 Appendix C Programming Example...
Page 109: ......