Rockwell Automation Publication 5069-UM003A-EN-P - May 2018
Chapter 3
Compact 5000 I/O Serial Module Features
Modbus Slave Functions
For Modbus Master and Modbus Slave Sample code, see
.
Table 9 - Inter-frame Timeout Minimum Values (11 Bit)
Baud Rate
Default Value
1Byte (11Bit)
3.5t (11Bit)
Legal Range (11Bit)
1200
64000
9166.667
32083.333
32000…65535000 (us)
2400
32000
4583.333
16041.667
16000…65535000 (us)
4800
16000
2291.667
8020.833
8000…65535000 (us)
9600
8000
1145.833
4010.417
4000…65535000 (us)
19200
3500
572.917
2005.208
1750…65535000 (us)
38400
3500
286.458
1002.604
1750…65535000 (us)
57600
3500
190.972
668.403
1750…65535000 (us)
115200
3500
95.486
334.201
1750…65535000 (us)
Table 10 - Modbus Slave Configuration Parameters
Parameter
Definition
Available Options
Modbus Format
Selecting communication method of Modbus of each
channel.
• 0 = RTU (default)
• 1 = ASCII
– Intervals of up to one second may elapse between
characters within the message. Unless the user has
configured a longer timeout, an interval greater
than 1 second means an error has occurred.
Node Address
Numbers to identify all modules that are connected to
each channel. You must set a number not equal to 0.
• 1…247
(default = 1)
Inter-frame Timeout
Maximum delay time to receive Data of each channel
• 0 is not a valid value. Use
and
determine the minimum value.
Summary of Contents for 5069-SERIAL
Page 1: ...Compact 5000 I O Serial Module Catalog Number 5069 SERIAL User Manual OriginalInstructions...
Page 9: ...Rockwell Automation Publication 5069 UM003A EN P May 2018 9 Preface Notes...
Page 10: ...10 Rockwell Automation Publication 5069 UM003A EN P May 2018 Preface...
Page 88: ...88 Rockwell Automation Publication 5069 UM003A EN P May 2018 Appendix A Module Tags Notes...
Page 101: ...Rockwell Automation Publication 5069 UM003A EN P May 2018 103 Programming Example Appendix C...
Page 104: ...106 Rockwell Automation Publication 5069 UM003A EN P May 2018 Appendix C Programming Example...
Page 109: ......