Rockwell Automation Publication 5069-UM003A-EN-P - May 2018
83
Module Tags
Appendix A
I
xx
.DiagnosticSequenceCount
SINT
Increments for each time a distinct diagnostic condition is detected,
and when a distinct diagnostic condition transitions from detected
to not detected.
Set to zero by product reset or power cycle. Wraps from 255 (-1) to 1
skipping zero.
-128…127
The value of 0 is skipped except during
module power-up.
I
xx
.Fault
BOOL
Indicates that channel data is inaccurate and cannot be trusted for
use in the application.
• 0 = Good
• 1 = Bad, causing fault
If the tag is set to 1, you must
troubleshoot the module to correct the
cause of the inaccuracy.
IMPORTANT
: Once the condition that
causes the tag to change to 1 is
removed, the tag automatically resets to
0.
I
xx
.Uncertain
BOOL
Indicates that the channel data can be inaccurate but the degree of
inaccuracy is not known.
• 0 = Good data
• 1 = Uncertain data
If the tag is set to 1, you must
troubleshoot the module to correct the
cause of the inaccuracy.
IMPORTANT
: Once the condition that
causes the tag to change to 1 is
removed, the tag automatically resets to
0.
I
xx
.LastExecutedCommand
SINT
Indicates the number of the latest executed command, and the
Update Counter indicates the status for command level. If this value
is updated, either a new command is executed, not changed,
command is not executed, or have not finished yet.
• -1(value shown prior to any command)
• 0…49
I
xx
.Command.
yy
.Fault
BOOL
Indicates that channel data is inaccurate and cannot be trusted for
use in the application.
The number of Commandyy tags (where yy can be 0…49) are
dynamically created depending on the command list you create.
• 0 = Good
• 1 = Bad, causing fault
If the tag is set to 1, you must
troubleshoot the module to correct the
cause of the inaccuracy.
IMPORTANT
: Once the condition that
causes the tag to change to 1 is
removed, the tag automatically resets to
0.
I
xx
.Command.
yy
.Uncertain
BOOL
Indicates that the channel data can be inaccurate but the degree of
inaccuracy is not known.
• 0 = Good data
• 1 = Uncertain data
If the tag is set to 1, you must
troubleshoot the module to correct the
cause of the inaccuracy.
IMPORTANT
: Once the condition that
causes the tag to change to 1 is
removed, the tag automatically resets to
0.
I
xx
.Command.
yy
.ParityError
BOOL
Status that shows whether a parity error has occurred or not.
• 0 = Non-occurrence
• 1 = Occurrence
I
xx
.Command.
yy
.ResponseTimeout
BOOL
Shows if there was a response timeout.
• 0 = Non-occurrence
• 1 = Occurrence
I
xx
.Command.
yy
.FramingError
BOOL
Shows if there was a framing error.
• 0 = Non-occurrence
• 1 = Occurrence
I
xx
.Command.
yy
.BufferOverRun
BOOL
Shows if a buffer overrun has occurred.
• 0 = Non-occurrence
• 1 = Occurrence
Table 19 - Modbus Master Input Tags
Name
Data Type
Definition
Valid Values
Summary of Contents for 5069-SERIAL
Page 1: ...Compact 5000 I O Serial Module Catalog Number 5069 SERIAL User Manual OriginalInstructions...
Page 9: ...Rockwell Automation Publication 5069 UM003A EN P May 2018 9 Preface Notes...
Page 10: ...10 Rockwell Automation Publication 5069 UM003A EN P May 2018 Preface...
Page 88: ...88 Rockwell Automation Publication 5069 UM003A EN P May 2018 Appendix A Module Tags Notes...
Page 101: ...Rockwell Automation Publication 5069 UM003A EN P May 2018 103 Programming Example Appendix C...
Page 104: ...106 Rockwell Automation Publication 5069 UM003A EN P May 2018 Appendix C Programming Example...
Page 109: ......